Designation D117 − 10 Standard Guide for Sampling, Test Methods, and Specifications for Electrical Insulating Oils of Petroleum Origin1 This standard is issued under the fixed designation D117; the nu[.]

Trang 1

Designation: D11710

Standard Guide for

Sampling, Test Methods, and Specifications for Electrical

This standard is issued under the fixed designation D117; the number immediately following the designation indicates the year of

original adoption or, in the case of revision, the year of last revision A number in parentheses indicates the year of last reapproval A

superscript epsilon (´) indicates an editorial change since the last revision or reapproval.

1 Scope

1.1 This guide describes methods of testing and

specifica-tions for electrical insulating oils of petroleum origin intended

for use in electrical cables, transformers, oil circuit breakers,

and other electrical apparatus where the oils are used as

insulating, or heat transfer media, or both

1.2 The purpose of this guide is to outline the applicability

of the available test methods Where more than one is available

for measuring a given property, their relative advantages are

described, along with an indication of laboratory convenience,

precision, (95 % confidence limits), and applicability to

spe-cific types of electrical insulating oils

1.3 This guide is classified into the following categories:

Sampling Practices, Physical Tests, Electrical Tests, Chemical

Tests, and Specifications Within each test category, the test

methods are listed alphabetically by property measured A list

of standards follows:

Category Section ASTM Method

Physical Tests:

Aniline Point 4 D611

Coefficient of Thermal

Ex-pansion

5 D1903

Examination: Visual Infrared 7 D1524, D2144

Flash and Fire Point 8 D92

Interfacial Tension 9 D971, D2285

Pour Point of Petroleum

Products

10 D97 Particle Count in Mineral

Insulating Oil

11 D6786 Refractive Index 12 D1218, D1807

Relative Density (Specific

Gravity)

13 D287, D1217, D1298, D1481 Specific Heat 14 D2766

Category Section ASTM Method Thermal Conductivity 15 D2717

Viscosity 17 D88, D445, D2161

Electrical Tests:

Dielectric Breakdown Voltage 18 D877, D1816, D3300 Dissipation Factor and

Rela-tive Permittivity (Dielectric Constant)

19 D924

Gassing Characteristic Under Thermal Stress

20 D7150 Gassing Tendency 21 D2300 Resistivity 22 D1169 Stability Under Electrical

Discharge

23 D6180

Chemical Tests:

Acidity, Approximate 24 D1534 Carbon-Type Composition 25 D2140 Compatibility with

Construc-tion Material

26 D3455 Copper Content 27 D3635 Elements by Inductively

Coupled Plasma (ICP-AES)

28 D7151 Furanic Compounds in

Electrical Insulating Liquids

29 D5837 Gas Analysis 30 D3612 Gas Content 31 D831, D1827, D2945 Inorganic Chlorides and

Sulfates

32 D878 Neutralization (Acid and

Base) Numbers

33 D664, D974 Oxidation Inhibitor Content 34 D2668, D4768 Oxidation Stability 35 D1934, D2112, D2440 Polychlorinated Biphenyl

Content

36 D4059 Relative Content of

Dissolved Decay

37 D6802 Sediment and Soluble Sludge 38 D1698 Sulfur, Corrosive 39 D1275 Water Content 40 D1533

Specification:

Mineral Insulating Oil for Electrical Apparatus

41 D3487 High Firepoint Electrical

Insulating Oils

42 D5222

1.4 The values stated in SI units are to be regarded as standard The values stated in parentheses are provided for information only

1 This guide is under the jurisdiction of ASTM Committee D27 on Electrical

Insulating Liquids and Gasesand is the direct responsibility of Subcommittee

D27.01 on Mineral.

Current edition approved Sept 15, 2010 Published October 2010 Originally

published as D117 – 21 T Last previous edition approved in 2002 as D117 – 02.

DOI: 10.1520/D0117-10.

Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959 United States

Trang 2

1.5 This standard does not purport to address all of the

safety concerns, if any, associated with its use It is the

responsibility of the user of this standard to establish

appro-priate safety and health practices and determine the

applica-bility of regulatory limitations prior to use.

2 Referenced Documents

2.1 ASTM Standards:2

D88Test Method for Saybolt Viscosity

D92Test Method for Flash and Fire Points by Cleveland

Open Cup Tester

D97Test Method for Pour Point of Petroleum Products

D287Test Method for API Gravity of Crude Petroleum and

Petroleum Products (Hydrometer Method)

D445Test Method for Kinematic Viscosity of Transparent

and Opaque Liquids (and Calculation of Dynamic

Viscos-ity)

D611Test Methods for Aniline Point and Mixed Aniline

Point of Petroleum Products and Hydrocarbon Solvents

D664Test Method for Acid Number of Petroleum Products

by Potentiometric Titration

D831Test Method for Gas Content of Cable and Capacitor

Oils

D877Test Method for Dielectric Breakdown Voltage of

Insulating Liquids Using Disk Electrodes

D878Test Method for Inorganic Chlorides and Sulfates in

Insulating Oils

D923Practices for Sampling Electrical Insulating Liquids

D924Test Method for Dissipation Factor (or Power Factor)

and Relative Permittivity (Dielectric Constant) of

Electri-cal Insulating Liquids

D971Test Method for Interfacial Tension of Oil Against

Water by the Ring Method

D974Test Method for Acid and Base Number by

Color-Indicator Titration

D1169Test Method for Specific Resistance (Resistivity) of

Electrical Insulating Liquids

D1217Test Method for Density and Relative Density

(Spe-cific Gravity) of Liquids by Bingham Pycnometer

D1218Test Method for Refractive Index and Refractive

Dispersion of Hydrocarbon Liquids

D1250Guide for Use of the Petroleum Measurement Tables

D1275Test Method for Corrosive Sulfur in Electrical

Insu-lating Oils

D1298Test Method for Density, Relative Density, or API

Gravity of Crude Petroleum and Liquid Petroleum

Prod-ucts by Hydrometer Method

D1481Test Method for Density and Relative Density

(Spe-cific Gravity) of Viscous Materials by Lipkin Bicapillary

Pycnometer

D1500Test Method for ASTM Color of Petroleum Products

(ASTM Color Scale)

D1524Test Method for Visual Examination of Used

Elec-trical Insulating Oils of Petroleum Origin in the Field

D1533Test Method for Water in Insulating Liquids by Coulometric Karl Fischer Titration

D1534Test Method for Approximate Acidity in Electrical Insulating Liquids by Color-Indicator Titration

D1698Test Method for Sediments and Soluble Sludge in Service-Aged Insulating Oils

D1807Test Methods for Refractive Index and Specific Optical Dispersion of Electrical Insulating Liquids

D1816Test Method for Dielectric Breakdown Voltage of Insulating Liquids Using VDE Electrodes

D1827Test Method for Gas Content (Nonacidic) of Insulat-ing Liquids by Displacement with Carbon Dioxide (With-drawn 2009)3

D1903Practice for Determining the Coefficient of Thermal Expansion of Electrical Insulating Liquids of Petroleum Origin, and Askarels

D1934Test Method for Oxidative Aging of Electrical Insu-lating Petroleum Oils by Open-Beaker Method

D2112Test Method for Oxidation Stability of Inhibited Mineral Insulating Oil by Pressure Vessel

D2140Practice for Calculating Carbon-Type Composition

of Insulating Oils of Petroleum Origin

D2144Practices for Examination of Electrical Insulating Oils by Infrared Absorption

D2161Practice for Conversion of Kinematic Viscosity to Saybolt Universal Viscosity or to Saybolt Furol Viscosity

D2285Test Method for Interfacial Tension of Electrical Insulating Oils of Petroleum Origin Against Water by the Drop-Weight Method(Withdrawn 2008)3

D2300Test Method for Gassing of Electrical Insulating Liquids Under Electrical Stress and Ionization (Modified Pirelli Method)

D2440Test Method for Oxidation Stability of Mineral Insulating Oil

D2668Test Method for di-tert-Butyl- p-Cresol and 2,6-di-tert-Butyl Phenol in Electrical Insulating Oil by

Infra-red Absorption

D2717Test Method for Thermal Conductivity of Liquids

D2759Practice for Sampling Gas from a Transformer Under Positive Pressure

D2766Test Method for Specific Heat of Liquids and Solids

D2945Test Method for Gas Content of Insulating Oils (Withdrawn 2012)3

D3300Test Method for Dielectric Breakdown Voltage of Insulating Oils of Petroleum Origin Under Impulse Con-ditions

D3305Practice for Sampling Small Gas Volume in a Trans-former

D3455Test Methods for Compatibility of Construction Ma-terial with Electrical Insulating Oil of Petroleum Origin

D3487Specification for Mineral Insulating Oil Used in Electrical Apparatus

D3612Test Method for Analysis of Gases Dissolved in Electrical Insulating Oil by Gas Chromatography

D3635Test Method for Dissolved Copper In Electrical

2 For referenced ASTM standards, visit the ASTM website, www.astm.org, or

contact ASTM Customer Service at service@astm.org For Annual Book of ASTM

Standards volume information, refer to the standard’s Document Summary page on

the ASTM website.

3 The last approved version of this historical standard is referenced on www.astm.org.

Trang 3

Insulating Oil By Atomic Absorption Spectrophotometry

D4052Test Method for Density, Relative Density, and API

Gravity of Liquids by Digital Density Meter

D4059Test Method for Analysis of Polychlorinated

Biphe-nyls in Insulating Liquids by Gas Chromatography

D4768Test Method for Analysis of 2,6-Ditertiary-Butyl

Para-Cresol and 2,6-Ditertiary-Butyl Phenol in Insulating

Liquids by Gas Chromatography

D5185Test Method for Multielement Determination of

Used and Unused Lubricating Oils and Base Oils by

Inductively Coupled Plasma Atomic Emission

Spectrom-etry (ICP-AES)

D5222Specification for High Fire-Point Mineral Electrical

Insulating Oils

D5837Test Method for Furanic Compounds in Electrical

Insulating Liquids by High-Performance Liquid

Chroma-tography (HPLC)

D6180Test Method for Stability of Insulating Oils of

Petroleum Origin Under Electrical Discharge

D6181Test Method for Measurement of Turbidity in

Min-eral Insulating Oil of Petroleum Origin (Withdrawn

2012)3

D6786Test Method for Particle Count in Mineral Insulating

Oil Using Automatic Optical Particle Counters

D6802Test Method for Determination of the Relative

Con-tent Of Dissolved Decay Products in Mineral Insulating

Oils by Spectrophotometry

D7150Test Method for the Determination of Gassing

Char-acteristics of Insulating Liquids Under Thermal Stress at

Low Temperature

D7151Test Method for Determination of Elements in

Insu-lating Oils by Inductively Coupled Plasma Atomic

Emis-sion Spectrometry (ICP-AES)

SAMPLING

3 Sampling

3.1 Accurate sampling, whether of the complete contents or

only parts thereof, is extremely important from the standpoint

of evaluation of the quality of the product sampled Obviously,

careless sampling procedure or contamination in the sampling

equipment will result in a sample that is not truly

representa-tive This generally leads to erroneous conclusions concerning

quality and incurs loss of the time, effort, and expense involved

in securing, transporting, and testing the sample

3.2 Sample the insulating oil in accordance with Practices

D923,D2759andD3305as appropriate

PHYSICAL PROPERTIES

4 Aniline Point

4.1 Scope—This test method covers the determination of the

aniline point of petroleum products, provided that the aniline

point is below the bubble point and above the solidification

point of the aniline-sample mixture

4.2 Summary of Test Method:

4.2.1 Test Method D611 —Equal volumes of aniline and test

specimen or aniline and test specimen plus n-heptane are

placed in a tube and mixed mechanically The mixture is heated

at a controlled rate until the two phases become miscible The mixture is then cooled at a controlled rate, and the temperature

at which the two phases separate is recorded as the aniline point

4.3 Significance and Use—The aniline point of an insulating

oil indicates the solvency of the oil for some materials that are

in contact with the oil A higher aniline point implies a lower aromaticity and a lower degree of solvency for some materials

5 Coefficient of Thermal Expansion

5.1 Scope—This test method covers the determination of the

coefficient of thermal expansion of electrical insulating liquids

of petroleum origin

5.2 Definition:

5.2.1 coeffıcient of thermal expansion—the change in

vol-ume per unit volvol-ume per degree change in temperature It is commonly stated as the average coefficient over a given temperature range

5.3 Summary of Test Method—The specific gravity of

insu-lating oils is determined at two temperatures below 90°C and separated by not less than 5°C nor more than 14°C Test methods used may be D287, D1217,D1298, or D1481 The calculation of average coefficient of thermal expansion over this temperature range is given in Test Method D1903

5.4 Significance and Use—A knowledge of the coefficient of

expansion of a liquid is essential to compute the required size

of a container to accommodate a volume of liquid over the full temperature range to which it will be subjected It is also used

to compute the volume of void space that would exist in an inelastic device filled with the liquid after the liquid has cooled

to a lower temperature

6 Color

6.1 Scope—This test method covers the visual

determina-tion of color of a wide variety of liquid petroleum products, including mineral insulating oils

6.2 Summary of Test Method:

6.2.1 Test Method D1500 —The test specimen is placed in a

glass sample jar (an ordinary 125-mL test specimen bottle is satisfactory for routine tests) The color of the sample by transmitted light is compared with a series of tinted glass standards The glass standard matching the sample is selected,

or if an exact match is not possible, the next darker glass is selected The results are reported numerically on a scale of 0.5

to 8.0

6.3 Significance—A low color number is an essential

re-quirement for inspection of assembled apparatus in a tank An increase in the color number during service is an indicator of deterioration or contamination of the insulating oil

7 Examination

7.1 Scope:

7.1.1 Both visual examination and qualitative infrared ab-sorption are described in this section The test methods are:

7.1.2 Test Method D1524 —This is a visual examination of

mineral insulating oils that have been used in transformers, oil

Trang 4

circuit breakers, or other electrical apparatus as insulating or

cooling media, or both This test is intended for use in the field

7.1.3 Test Method D2144 —The infrared absorption from 2.5

to 25 µm (4000 to 667 cm−1) is recorded as a means of (a)

establishing continuity by comparison with the spectra of

previous shipments by the same supplier, (b) for the detection

of some types of contaminants, (c) for the identification of oils

in storage or service This test method is not intended for the

determination of the various constituents of an oil

7.2 Summary of Test Methods:

7.2.1 Test Method D1524 —Estimate the color of the oil by

use of an oil comparator, matching the oil test specimen with

tinted glass color standards Note the presence of cloudiness,

particles of insulation, metal corrosion products, or other

undesirable suspended materials in the oil

7.2.2 Test Methods D2144 —The infrared spectrum is

re-corded from 2.5 to 25 µm (4000 to 667 cm−1) either as the

absorption spectrum itself, or as the differential between the

test specimen and reference oil The spectra are compared with

reference spectra to establish the identity of the oil

7.3 Significance and Use:

7.3.1 Test Method D1524 —The observation of the color and

condition of the oil in a field inspection permits a determination

of whether the sample should be sent to a central laboratory for

full evaluation

7.3.2 Test Methods D2144 —The infrared spectrum of an

electrical insulating oil indicates the general chemical

compo-sition of the sample Because of the complex mixture of

compounds present in insulating oils, the spectrum is not

sharply defined and may not be suitable for quantitative

estimation of components The identity of the oil can be

quickly established as being the same or different from

previous samples by comparison with the reference spectra

8 Flash and Fire Point

8.1 Scope:

8.1.1 This test method covers the determination of flash and

fire points of all petroleum products except fuel oils and those

having an open cup flash below 79°C (175°F)

8.1.2 This test method should be used solely to measure and

describe the properties of materials in response to heat and

flame under controlled laboratory conditions and should not be

used for the description, appraisal, or regulation of the fire

hazard of materials under actual fire conditions

8.2 Definitions:

8.2.1 flash point—the temperature at which vapors above

the oil surface first ignite when a small test flame is passed

across the surface under specified conditions

8.2.2 fire point—the temperature at which oil first ignites

and burns for at least 5 s when a small test flame is passed

across the surface under specified conditions

8.3 Summary of Test Method—Fill the test cup to the

specified level with the test specimen Heat the sample initially

at 14 to 17°C/min (25 to 30°F/min) until the temperature is

56°C (100°F) below the expected flash point Reduce the rate

of temperature change to 5 to 6°C/min (9 to 11°F/min) and

apply the test flame every 2°C (or 5°F) until a flash occurs

Continue heating and testing every 2°C (or 5°F) until the oil continues to burn for at least 5 s The procedure is described in Test Method D92

8.4 Significance and Use—The flash point and fire point

tests give an indication of the flammability of an oil They may also be used to provide a qualitative indication of contamina-tion with more flammable materials In the latter context, the flash point test is more sensitive

9 Interfacial Tension

9.1 Scope—These test methods cover the measurement,

under nonequilibrium conditions, of the interfacial tension of insulating oils against water These test methods have been shown by experience to give a reliable indication of the presence of hydrophilic compounds

9.2 Definition:

9.2.1 interfacial tension—the molecular attractive force

be-tween unlike molecules at an interface It is usually expressed

in dynes per centimetre or millinewtons per metre

9.3 Summary of Test Methods:

9.3.1 Test Method D971 —Interfacial tension is determined

by measuring the force necessary to detach a platinum wire upward from the oil-water interface To calculate the interfacial tension, the force so measured is corrected by an empirically determined factor which depends upon the force applied, the densities of both oil and water, and the dimensions of the ring The measurement is completed within 1 min of the formation

of the interface

9.3.2 Test Method D2285 —Interfacial tension is determined

by measuring the volume of a drop of water that the oil will support The larger the drop of water, the higher the interfacial tension of the oil The instrument used to measure the volume

of the drops of water is calibrated to read approximately in dynes per centimeter interfacial tension For better accuracy, the reading can be corrected by a factor that depends on the density of the oil The drop is allowed to age for 30 s and to fall between 45 and 60 s after formation

9.4 Significance and Use—Interfacial tension measurements

on electrical insulating oils provide a sensitive means of detecting small amounts of soluble polar contaminants and products of oxidation A high value for new mineral insulating oil indicates the absence of undesirable polar contaminants The test is frequently applied to service-aged oils as an indication of the degree of deterioration

10 Pour Point

10.1 Scope—The pour point is applicable to any petroleum

oil

10.2 Definition:

10.2.1 pour point—the lowest temperature, expressed as a

multiple of 3°C at which the oil is observed to flow when cooled and examined under prescribed conditions

10.3 Summary of Test Method—After preliminary heating,

the test specimen is cooled at a specified rate and examined at

Trang 5

intervals of 3°C for flow characteristics The lowest

tempera-ture at which movement of the oil is observed within 5 s is

reported as the pour point The procedure is described in Test

MethodD97

10.4 Significance and Use:

10.4.1 The pour point of an insulating oil gives an

indica-tion of the temperature below which it may not be possible to

pour or remove the oil from its container

10.4.2 In connection with oil for use in cable systems, the

pour point may be useful to indicate the point at which no free

movement will take place in the cable or to indicate the

temperature at which partial separation of wax may occur

10.4.3 The pour point of a transformer oil is important as an

index of the lowest temperature to which the material may be

cooled without seriously limiting the degree of circulation of

the oil Some materials are sensitive to temperature cycling or

prolonged storage at low temperatures, and their pour points

may not adequately predict their low temperature flow

prop-erties

11 Particle Count in Mineral Insulating Oil Using

Automatic Opticle Particle Counters

11.1 Scope—This test method covers the determination of

particle concentration and particle size distribution in mineral

insulating oil It is suitable for testing oils having a viscosity of

6 to 20 cSt at 40°C The test method is specific to liquid

automatic particle analyzers that use the light extinction

principle

11.2 Summary of Test Method:

11.2.1 Samples are taken in particle-clean bottles that are

suitable for particle analysis The sample bottle is agitated to

redistribute particles in the oil, then the oil is placed in an

automatic particle counter, where the number of particles and

their size distribution are determined by the light extinction

principle

11.2.2 As particles pass through the sensing zone of the

instrument, the quantity of light reaching the detector is

obscured This signal is translated to an equivalent projected

area diameter based on calibration with a NIST-traceable fluid

(ISO Medium Test Dust suspension)

11.3 Significance and Use:

11.3.1 Particles in insulating oil can have a detrimental

effect on the dielectric properties of the fluid, depending on the

size, concentration, and nature of the particles The source of

these particles can be external contaminants, oil degradation

byproducts, or internal materials such as metals, carbon, or

cellulose fibers

11.3.2 Particle counts provide a general degree of

contami-nation level and may be useful in assessing the condition of

specific types of electrical equipment Particle counts can also

be used to determine filtering effectiveness when processing

oil

11.3.3 If more specific knowledge of the nature of the

particles is needed, other tests such as metals analysis or fiber

identification and counting must be performed

12 Refractive Index and Specific Optical Dispersion

12.1 Scope:

12.1.1 Test Method D1218 —Describes a precision method

for determining refractive index accurate to 0.00006 and refractive dispersion accurate to 0.00012 The liquid must be transparent, no darker than ASTM 4.0 color (see Test Method D1500) and have a refractive index between 1.33 and 1.50 The specific optical dispersion is calculated by dividing the refrac-tive dispersion value by the specific gravity of the liquid

12.1.2 Test Method D1807 —Describes a routine method for

measuring refractive index accurate to three units in the fourth decimal place, measuring refractive dispersion, and calculating specific optical dispersion accurate to three units in the fourth decimal place The oils must be transparent and light colored

12.2 Definitions:

12.2.1 refractive index—the ratio of the velocity of light in

air to its velocity in the substance under test

12.2.2 specific optical dispersion —the difference between

the refractive indexes of light of two different wave lengths, both indexes measured at the same temperature, the difference being divided by the specific gravity also measured at the test temperature For convenience, the specific dispersion value is multiplied by 104

12.3 Summary of Test Method:

12.3.1 The two methods differ in the accuracy of the refractometer used After adjusting the instrument temperature

to 25°C, apply the test specimen to the refracting prism, read the refractive index, and read the compensator dial reading From the correlation tables supplied with the instrument obtain the refractive dispersion Calculate the specific optical disper-sion by dividing refractive disperdisper-sion by the specific gravity of the oil

12.4 Significance and Use:

12.4.1 Refractive Index of an insulating liquid varies with

its composition and with the nature and amount of contami-nants held in solution Where the refractive index of an insulating liquid when new is known, determinations made on the same liquid after periods of service may form a basis for estimating any change in composition or the degree of con-tamination acquired through solution

12.4.2 Specific Optical Dispersion serves as a quick index

to the amount of unsaturated compounds present in an oil As the dispersion values for paraffinic and naphthenic compounds are nearly the same and are essentially independent of molecu-lar weight and structural differences, values above a minimum

of about 97 bear a direct relationship to the amount of aromatic compounds present in insulating oil

13 Relative Density (Specific Gravity)

13.1 Scope:

13.1.1 The methods used to measure relative density (spe-cific gravity) may use a hydrometer, pycnometer, or an oscillating tube

13.1.1.1 Test Method D287 —Uses an API hydrometer and is

limited to liquids having a Reid vapor pressure of 180 kPa (26 psi) or less

13.1.1.2 Test Method D1217 —Covers the use of a

pycnom-eter to measure the relative density (specific gravity) of petroleum fractions

Trang 6

13.1.1.3 Test Method D1298 —Covers the use of a

hydrom-eter to measure relative density (specific gravity) directly or the

measurement of API gravity followed by conversion to relative

density (specific gravity) This test method is limited to liquids

having a Reid vapor pressure of 179 kPa (26 psi) or less This

test method is most suitable for use with mobile transparent

liquids, although it can also be used with viscous oils if

sufficient care is taken in the measurement

13.1.1.4 Test Method D1481 —Covers the determination of

the densities of oils more viscous than 15 cSt at 20°C The

liquid should not have a vapor pressure greater than 13 kPa

(100 mm Hg) at the test temperature To measure the density of

less viscous liquids more accurately than permitted by the

hydrometer method, Test MethodD1217is available

13.1.1.5 Test Method D4052 —Covers the measurement of

relative density (specific gravity) by the measurement of

change in oscillation frequency of a vibrating glass tube filled

with test liquid

13.2 Definition:

13.2.1 relative density (specific gravity)—the ratio of the

mass (weighed in vacuum) of a given volume of liquid at

15.6°C (60°F) to the mass of an equal volume of pure water at

the same temperature When reporting results, explicitly state

the reference temperature, for example, specific gravity 15.6/

15.6°C

13.3 Summary of Test Method:

13.3.1 API gravity may be measured at the oil temperature

using a hydrometer (Test Methods D287 or D1298) and

converting to 15.6°C using GuideD1250

13.3.2 Relative density (specific gravity) may be measured

at the oil temperature using a hydrometer (Test MethodD1298)

and converted to 15.6°C using Guide D1250

13.3.3 Test Method D1481 —The liquid is drawn into the

bicapillary pycnometer through the removable siphon arm and

adjusted to volume at the temperature of test After

equilibra-tion at the test temperature, liquid levels are read; and the

pycnometer is removed from the thermostated bath, cooled to

room temperature, and weighed Density or relative density

(specific gravity), as desired, is then calculated from the

volume at the test temperature, and the weight of the sample

The effect of air buoyancy is included in the calculation

13.4 Significance and Use:

13.4.1 Electrical insulating oils are usually sold on the basis

of volume delivered at 15.6°C (60°F) Delivery is often made

on the basis of net weight of product in drums, and the specific

gravities often are measured at temperatures other than 15.6°C

The values of relative density (specific gravity) at 15.6°C must

be known to calculate the volume at 15.6°C of the oil

delivered

13.4.2 The relative density (specific gravity) of a mineral

insulating oil influences the heat transfer rates and may be

pertinent in determining suitability for use in specific

applica-tions In certain cold climates, ice may form in de-energized

transformers exposed to temperatures below 0°C, and the

maximum specific gravity of the oil used in such equipment

should be at a value that will ensure that ice will not float in the

oil at any temperature the oil might attain

13.4.3 When making additions of insulating liquid to appa-ratus in service, a difference in relative density (specific gravity) may indicate a tendency of the two bodies of liquid to remain in separate layers rather than mixing into a homoge-neous single body of liquid Such conditions have caused serious overheating of self-cooled apparatus Suitable precau-tions should be taken to ensure mixing

14 Specific Heat

14.1 Scope—This test method covers determination of the

specific heat of electrical insulating liquids of petroleum origin

14.2 Definition:

14.2.1 specific heat (or heat capacity) of a substance—a

thermodynamic property that is a measure of the amount of energy required to produce a given temperature change within

a unit quantity of that substance The standard unit of heat capacity is Joules/Kg°C at some defined temperature; specific heat is dimensionless as it is the ratio of the substance’s heat capacity relative to that of water

14.3 Summary of Test Method—The specific heat is

deter-mined by Test Method D2766 The measurement is made by heating a test specimen at a known and fixed rate Once dynamic heating equilibrium is obtained, the heat flow is recorded as a function of temperature The heat flow normal-ized to specimen mass and heating rate is directly proportional

to the specimen’s specific heat capacity

14.4 Significance and Use—A knowledge of the specific

heat is helpful in designing adequate heat transfer properties for electrical apparatus A higher specific heat value indicates a more efficient heat transfer medium

15 Thermal Conductivity

15.1 Scope—This test method covers the determination of

the thermal conductivity of electrical insulating liquids of petroleum origin

15.2 Definition:

15.2.1 thermal conductivity—the ability of a substance to

transfer energy as heat in the absence of mass transport phenomena The standard unit of thermal conductivity is as follows:

W/~mK! ~Cal/cm s °C!

15.3 Summary of Test Method—The thermal conductivity is

determined by Test MethodD2717 This test method measures the temperature gradient produced across the liquid by a known amount of energy introduced into the test cell by an electrically heated platinum element

15.4 Significance and Use—A knowledge of thermal

con-ductivity is helpful in designing adequate heat transfer prop-erties for electrical apparatus A high value indicates a good heat transfer efficiency property for the liquid

16 Turbidity

16.1 Scope—This test method determines the amount of

suspended particulate matter in electrical insulating oil of petroleum origin

16.2 Definition:

Trang 7

16.2.1 turbidity, n—the reduction of transparency due to

presence of particulate matter The standard unit of turbidity is

the nephelometric turbidity unit (NTU), which is defined as the

intensity of light scattered by a known aqueous suspension of

formazine

16.3 Summary of Test Method—The turbidity is determined

by Test Method D6181 This test method measures the

scat-tered light at 0.5 π rad (90°) or 0.5 and 1.5 π rad (90° and 270°)

angles to the incident beam using a nephelometer that has been

calibrated with a standard aqueous suspension of formazine

16.4 Significance and Use—Turbidity measures particulate

contamination in electrical insulating oil that may not be

apparent to the unaided human eye and could affect the

performance of the dielectric fluid

17 Viscosity

17.1 Scope:

17.1.1 Test Method D88 —Covers the empirical

measure-ment of Saybolt viscosity of petroleum products using the

Saybolt viscometer at temperatures between 25.1and 98.9°C

(70 and 210°F)

17.1.2 Test Method D445 —Covers the determination of the

kinematic viscosity of liquid petroleum products by measuring

the time for a volume of liquid to flow under gravity through

a calibrated glass capillary viscometer

17.1.3 Practice D2161 —Provides tables or equations for the

conversion of centistokes into Saybolt Universal Seconds or

Saybolt Furol Seconds at the same temperatures

17.2 Summary of Test Methods:

17.2.1 Test Method D88 —The efflux time in seconds for 60

mL of test specimen to flow through a calibrated orifice in the

Saybolt viscometer is measured under carefully controlled

conditions, particularly temperature and liquid head The time

is converted by an orifice factor and reported as the viscosity of

the sample at that temperature

17.2.2 Test Method D445 —The time is measured in seconds

for a fixed volume of liquid to flow under gravity through the

capillary of a calibrated viscometer under a reproducible

driving head and at a closely controlled temperature The

kinematic viscosity is the product of the measured flow time

and the calibration constant of the viscometer

17.2.3 Practice D2161 —The Saybolt Universal viscosity

equivalent to a given kinematic viscosity varies with the

temperature at which the determination is made The basic

conversion values are given in Table 1 of this practice for

37.8°C (100°F) Factors are given for converting units at other

temperatures The Saybolt Furol viscosity equivalents are

given in Table 3 of this practice for 50.0 and 98.9°C (122 and

210°F) only

17.3 Significance and Use:

17.3.1 The fundamental and preferred method for

measur-ing kinematic viscosity is by use of Test Method D445 The

Saybolt instrument in Test Method D88, being of all-metal

construction, may be more rugged for field use, but values

obtained are significantly less accurate than those obtained by

the use of the capillary viscometers in Test Method D445

17.3.2 Viscosity of electrical insulating oils influences their heat transfer properties, and consequently the temperature rise

of energized electrical apparatus containing the liquid At low temperatures, the resulting higher viscosity influences the speed of moving parts, such as those in power circuit breakers, switchgear, load tapchanger mechanisms, pumps, and regula-tors Viscosity controls insulating oil processing conditions, such as dehydration, degassification and filtration, and oil impregnation rates High viscosity may adversely affect the starting up of apparatus in cold climates (for example, spare transformers and replacements) Viscosity affects pressure drop, oil flow, and cooling rates in circulating oil systems, such

as in pipe-type cables and transformers

ELECTRICAL PROPERTIES

18 Dielectric Breakdown Voltage

18.1 Scope:

18.1.1 There are two standard test methods for determining the dielectric breakdown voltage of electrical insulating fluids

at commercial power frequencies, D877andD1816, and one standard test method for determining the dielectric breakdown voltage of insulating oils under impulse conditions,D3300

18.1.2 Test Method D877 —Applicable to liquid petroleum

oils, hydrocarbons, and askarels commonly used as insulating and cooling media in cables, transformers, oil circuit breakers, and similar apparatus The suitability of Test MethodD877for testing liquids having viscosities exceeding 900 cSt (5000 SUS) at 40°C (104°F) has not been determined

18.1.3 Test Method D1816 —Applicable to liquid petroleum

oils commonly used as an insulating and cooling medium in cables, transformers, oil circuit breakers, and similar apparatus The suitability of Test Method D1816for testing oils having viscosities of more than 19 cSt (100 SUS) at 40°C (104°F) has not been determined

18.1.4 Test Method D3300 —Applicable to any liquid

com-monly used as an insulating and cooling medium in high-voltage apparatus subjected to impulse conditions, such as transient voltage stresses arising from such causes as nearby lightning strikes and high-voltage switching operations

18.2 Definition:

18.2.1 dielectric breakdown voltage—the potential

differ-ence at which electrical failure occurs in an electrical insulating material or insulation structure, under prescribed test condi-tions

18.3 Summary of Test Methods:

18.3.1 Test Method D877 —The insulating liquid is tested in

a test cup between two 25.4-mm (1-in.) diameter disk elec-trodes spaced 2.54 mm (0.100 in.) apart A 60-Hz voltage is applied between the electrodes and raised from zero at a uniform rate of 3 kV/s The dielectric breakdown voltage is recorded, prior to the occurrence of disruptive discharge, when the voltage across the specimen has dropped to less than 100 V

In the referee procedure, one breakdown test is made on each

of five fillings of the test cup, and the average and individual values of breakdown voltage are reported

18.3.2 Test Method D1816 —The oil is tested in a test cell

between spherically capped (VDE) electrodes spaced either 1

Trang 8

mm (0.040 in.) or 2 mm (0.080 in.) apart The oil is stirred

before and during application of voltage by means of a

motor-driven stirrer A 60-Hz voltage is applied between the

electrodes and raised from zero at a uniform rate of1⁄2 kV/s

The voltage at which the current produced by breakdown of the

oil reaches the range of 2 to 20 mA, tripping a circuit breaker,

is considered to be the dielectric breakdown voltage In the

procedure, five breakdown tests are made on one filling of the

test cell If the five breakdowns fall within the statistical

requirements, the average value is reported If not, five

additional breakdowns are required with the average of the ten

values reported

18.3.3 Test Method D3300 —The electrode system consists

of either: (1) two 12.7-mm (0.5-in.) diameter spheres spaced

3.8 mm (0.15 in.) apart or (2) a 12.7-mm (0.5-in.) diameter

sphere and a steel phonograph needle of 0.06-mm radius of

curvature of point, spaced 25.4 mm (1.0 in.) apart The polarity

of the needle with respect to the sphere can be either positive

or negative The electrodes are immersed in the oil in a test

cell An impulse wave of 1.2by 50 µs wave shape (times to

reach crest value and to decay to half of crest value,

respec-tively) is applied at progressively higher voltages until

break-down occurs

18.4 Significance and Use:

liquid at commercial power frequencies is of importance as a

measure of the liquid’s ability to withstand electric stress It is

the voltage at which breakdown occurs between two electrodes

under prescribed test conditions It also serves to indicate the

presence of contaminating agents, such as water, dirt, moist

cellulosic fibers, or conducting particles in the liquid, one or

more of which may be present when low dielectric breakdown

values are found by test However, a high dielectric breakdown

voltage does not indicate the absence of all contaminants See

Appendix X1 of either test method for other influences that

affect the dielectric breakdown voltage of a liquid

18.4.1.1 The ability of a fluid to resist breakdown under the

test conditions is an indication of the ability of the fluid to

perform its insulating function in electrical apparatus The

average breakdown voltage is commonly used in specifications

for the qualification and acceptance of insulating fluids It is

also used as a control test for the refining of new or reclaiming

of used insulating fluids Because of the complex interactions

of the factors affecting dielectric breakdown voltage the values

obtained cannot be used for design purposes

18.4.1.2 The square-edged disk electrodes of Test Method

D877 are relatively insensitive to dissolved water in

concen-trations below 60 % of the saturation level This method is

recommended for acceptance tests on unprocessed insulating

liquids received from vendors in tank cars, tank trucks, and

drums It also may be used for the routine testing of liquids

from selected power systems apparatus

18.4.1.3 The more uniform electric field associated with

VDE electrodes employed in Test Method D1816 is more

sensitive to the deleterious effects of moisture in solution,

especially when cellulosic fibers are present in the oil, than is

the field in Test MethodD877 Test MethodD1816can be used

for processed or as received oils Filtering and dehydrating the oil may increase Test Method D1816 dielectric breakdown voltages substantially

18.4.2 Impulse Conditions (Test Method D3300 ):

18.4.2.1 This test method is most commonly performed using a negative polarity point opposing a grounded sphere (NPS) The NPS breakdown voltage of fresh unused oils measured in the highly divergent field in this configuration depends on oil composition; decreasing with increasing con-centration of aromatic, particularly polyaromatic, hydrocarbon molecules

18.4.2.2 This test method may be used to evaluate the continuity of composition of an oil from shipment to shipment The NPS impulse breakdown voltage of an oil can also be substantially lowered by contact with materials of construction,

by service aging, and by other impurities Test results lower than those expected for a given fresh oil may also indicate use

or contamination of that oil

18.4.2.3 Although polarity of the voltage wave has little or

no effect on the breakdown strength of an oil in uniform fields, polarity does have a marked effect on the breakdown voltage of

an oil in nonuniform electric fields

19 Dissipation Factor and Relative Permittivity (Dielectric Constant)

19.1 Scope:

19.1.1 This test method covers new electrical insulating liquids as well as liquids in service or subsequent to service in cables, transformers, oil circuit breakers, and other electrical apparatus

19.1.2 This test method provides a procedure for making referee and routine tests at a commercial frequency of approxi-mately 60 Hz

19.2 Summary of Test Method:

19.2.1 The loss characteristic is commonly measured in terms of dissipation factor (tangent of the loss angle) or of power factor (sine of the loss angle) For values up to 0.05, dissipation factor and power factor values are equal to each other within about one part in one thousand and the two terms may be considered interchangeable

19.2.2 Test Method D924 —The oil test specimens are tested

in a three-terminal or guarded electrode test cell maintained at the desired test temperature Using a bridge circuit, measure the loss characteristics and capacitance following the instruc-tions appropriate to the bridge being used For routine tests, a two-electrode cell may be used

19.3 Significance and Use:

19.3.1 Dissipation Factor (or Power Factor)—This

prop-erty is a measure of the dielectric losses in an oil, and hence,

of the amount of energy dissipated as heat A low value of dissipation factor (or power factor) indicates low dielectric losses and a low level of soluble polar ionic or colloidal contaminants This characteristic may be useful as a means of quality control and as an indication of oil changes in service resulting from contamination and oil deterioration

19.3.2 Relative Permittivity (Dielectric Constant)—

Insulating liquids are used in general either to insulate com-ponents of an electrical network from each other and from

Trang 9

ground, alone or in combination with solid insulating materials,

or to function as the dielectric of a capacitor For the first use,

a low value of relative permittivity is often desirable in order

to have the capacitance be as small as possible, consistent with

acceptable chemical and heat transfer properties However, an

intermediate value of relative permittivity may sometimes be

advantageous in achieving a better voltage distribution

be-tween the liquid and solid insulating materials with which the

liquid may be in series When used as the dielectric in a

capacitor, it is desirable to have a higher value of relative

permittivity so the physical size of the capacitor may be as

small as possible

20 Gassing Characteristics of Insulating Liquids Under

Thermal Stress at Low Temperature

20.1 Scope:

20.1.1 This test method describes the procedures to

deter-mine the low temperature (120°C) gassing characteristics of

insulating liquids specifically and without the influence of

other electrical apparatus materials or electrical stresses This

test method was primarily designed for insulating mineral oil

It can be applied to other insulating liquids in which dissolved

gas-in-oil analysis (Test Method D3612) is commonly

per-formed

20.1.2 This test method is particularly suited for detection

of the phenomenon sometimes known as “stray gassing” and is

also referred to in CIGRE TF11 B39 1.3 This test method is

performed on transformer insulating liquids to determine the

propensity of the oil to produce certain gases such as hydrogen

and hydrocarbons at low temperatures

20.1.3 This test method details two procedures:

20.1.3.1 Method A describes the procedure for determining

the gassing characteristics of a new, unused insulating liquid,

as received, at 120°C for 164 h

20.1.3.2 Method B describes the procedure for processing

the insulating liquid through an attapulgite clay column to

remove organic contaminants and other reactive groups that

may influence the gassing behavior of an insulating liquid,

which is suspected of being contaminated This procedure

applies to both new and used insulating liquids

20.2 Summary of Test Method:

20.2.1 Method A—Insulating liquid is filtered through a

mixed cellulose ester filter A portion of the test specimen is

sparged for 30 min with dry air A test specimen is then placed

into a glass syringe, capped and aged at 120 6 2°C for 164 h

The test is run in duplicate The other portion of the test

specimen is sparged for 30 min with dry nitrogen A test

specimen is then placed into a glass syringe, capped and aged

at 120°C 6 2°C for 164 h The test is run in duplicate After,

the test specimens have cooled, dissolved gas-in-oil analysis is

then performed according to Test MethodD3612

20.2.2 Method B—Insulating oil is passed through a heated

(60 to 70°C) attapulgite clay column at a rate of 3 to 5 mL per

minute The insulating liquid is contacted with the attapulgite

clay at a ratio of 1 g clay to 33 mL (range: 30 to 35 mL) of

insulating liquid (0.25 lb clay: 1 gal of insulating liquid) The

insulating liquid is collected and subjected to the testing as

outlined in4.1

20.3 Significance and Use:

20.3.1 Generation of combustible gases is used to determine the condition of oil-filled electrical apparatus Many years of empirical evidence has yielded guidelines such as those given

in IEEE C 57.104, IEC 60599 and IEC 61464 Industry experience has shown that electric and thermal faulted in oil-filled electrical apparatus are the usual sources that generate gases Experience has shown that some of the gases could form

in the oil at low temperatures or as a result of contamination, without any other influences

20.3.2 Some severely hydro-treated transformer oils sub-jected to thermal stress and oils that contain certain types of contamination may produce specific gases at lower tempera-tures than normally expected for their generation and hence, falsely indicate abnormal operation of the electrical apparatus Some new oils have produced large amounts of gases, espe-cially hydrogen, without the influence of other electrical apparatus materials or electrical stresses This renders interpre-tation of the dissolved gas analysis more complicated 20.3.3 Heating for 164 h has been found to be a sufficient amount of time to reach a stable and characteristic gassing pattern

20.3.4 This method uses both dry air and dry nitrogen as the sparging gas This is to reflect either a electrical apparatus preservation system that allows oxygen to contact the oil or one that is sealed from the outside atmosphere Oils sparged with air generally produce much more hydrogen as a percentage of the total combustible gas content as compared to oils sparged with nitrogen as these produce more hydrocarbons in relation

to hydrogen

21 Gassing Tendency

21.1 Scope—Test MethodD2300 describes a procedure to measure the rate at which gas is evolved or absorbed by insulating oils when subjected to electrical stress of sufficient intensity to cause ionization The oil test specimen is initially saturated with a selected gas (usually hydrogen) at atmospheric pressure

21.2 Summary of Test Method:

21.2.1 Test Method D2300 —After being saturated with a

gas (usually hydrogen) the oil is subjected to a radial electrical stress at a controlled temperature The gas space above the oil

is ionized due to the electrical stresses; and therefore, the oil surface at the oil-gas interface is subjected to ion bombard-ment The evolution or absorption of gas is measured with a gas burette and reported in µL/min

21.3 Significance and Use—This test method indicates

whether insulating oils are gas absorbing or gas evolving under the test conditions Numerical results obtained in different laboratories may differ significantly in magnitude, and the results of this test method should be considered as qualitative

in nature

21.3.1 For certain applications when insulating oil is stressed at high voltage gradients, it is desirable to be able to determine the rate of gas evolution or gas absorption under specified test conditions At the present time, correlation of such test results with equipment performance is limited

Trang 10

22 Resistivity

22.1 Scope:

22.1.1 This test method covers the determination of specific

resistance (resistivity) applied to new electrical insulating

liquids, as well as to liquids in service, or subsequent to

service, in cables, transformers, circuit breakers, and other

electrical apparatus

22.1.2 This test method covers a procedure for making

referee and routine tests with dc potential

22.2 Definition:

22.2.1 specific resistance (resistivity)—of a liquid, the ratio

of the dc potential gradient in volts per centimetre paralleling

the current flow within the test specimen, to the current density

in amperes per square centimetre at a given instant of time and

under prescribed conditions This is numerically equal to the

resistance between opposite faces of a centimetre cube of a

liquid It is measured in ohm centimetres

22.3 Summary of Test Method:

22.3.1 Test Method D1169 —The oil test specimen is tested

in three-terminal, or guarded-electrode test cell maintained at

the desired test temperature A dc voltage is applied of such

magnitude that the electric stress in the liquid is between 200

and 1200 V/mm (5 to 30 V/mL) The current flowing between

the high-voltage and guarded measuring electrode is measured

at the end of 1 min of electrification and the resistivity

calculated using specified equations appropriate to the method

of measurement used A two-electrode cell may be used for

routine tests

22.4 Significance and Use—The resistivity of a liquid is a

measure of its electrical insulating properties under conditions

comparable to those of the test High resistivity reflects low

content of free ions and ion-forming particles and normally

indicates a low concentration of conductive contaminants

23 Stability Under Electric Discharge

23.1 Scope—Test Method D6180 measures the relative

stability of new, used, or reclaimed insulating oils of petroleum

origin in the presence of a controlled electric discharge by

monitoring the pressure increase in the evacuated discharge

chamber

23.2 Summary of Test Method—A test specimen is

intro-duced into a discharge cell and degassed under vacuum at room

temperature An ac potential of 10 KV is applied for 300 min

The gradual rise of pressure inside the discharge cell is

measured as a function of time The dissipation factor of the oil

at 100°C is determined before and after the stability test using

Test Method D924

23.3 Significance and Use—The changes observed in the

generation of gases as noted by pressure change and the

composition modification as reflected in dissipation factor

increases may provide a relative assessment of the stability of

the oil for high voltage application

CHEMICAL PROPERTIES

24 Acidity, Approximate

24.1 Scope—Test MethodD1534covers the determination

of the approximate total acid value of used electrical insulating

liquids, in general, those having viscosities less than 24 cSt at 40°C It is a simple procedure that can be applied in the field Where a quantitative neutralization value is required, use Test MethodD664orD974 These test methods should be applied

in the laboratory

24.2 Summary of Test Method:

24.2.1 Test Method D1534 —To determine whether the

acid-ity is greater or less than a fixed arbitrary value, a fixed volume

of liquid to be tested is added to the test bottle or graduated cylinder, together with a small amount of indicator (phenol-phthalein) and the appropriate quantity of standard potassium hydroxide solution The mixture is shaken and allowed to separate The color of the aqueous layer at the bottom of the container when testing mineral oils, or at the top when testing askarels, determines whether the acidity is less than or greater than the arbitrary value chosen

24.3 Significance and Use:

24.3.1 The approximate acidity of used electrical insulating oils is an estimate of the total acid value of the oil As acid values increase, usually due to oxidation of the oil in service, the impairment of those oil qualities, important to proper functioning of specific apparatus, increases In general, acidic by-products produce increased dielectric loss, increased corrosivity, and may cause thermal difficulties attributable to insoluble components called “sludge.” This test method is adapted to a specific volume of oil; total acid values of 0.05 to 0.5 mg of potassium hydroxide per gram of oil is a range which

is functionally significant

25 Carbon-Type Composition

25.1 Scope—This test method covers the determination of

carbon-type composition of insulating oils by correlation with basic physical properties Carbon-type composition is ex-pressed as percentage of aromatic carbons, percentage of naphthenic carbons, and percentage of paraffinic carbons Viscosity, relative density (or specific gravity), and refractive index are the only measurements required for use of this test method

25.2 Summary of Test Method:

25.2.1 Test Method D2140 —The viscosity, density and

spe-cific gravity, and refractive index of the oil are measured From these values, the viscosity-gravity constant and refractivity intercept are calculated Using these two computed values, percentage of aromatic carbons, naphthenic carbons, and paraffinic carbons are estimated from a correlation chart

25.3 Significance and Use—The primary purpose of this test

method is to characterize the carbon-type composition of an oil It is also applicable in observing the effect on oil consti-tution of various refining processes, such as solvent extraction, acid treatment, and so forth It has secondary application in relating the chemical nature of an oil to other phenomena that have been demonstrated to be related to oil composition

26 Compatibility with Construction Material

26.1 Scope—This test method covers screening for the

compatibility of materials of construction with electrical insu-lating oil for use in electrical equipment Solid materials that