Increased penetration of rooftop solar PV is causing undesirable technical impacts on the distribution networks. Several urban distribution transformers in Sri Lanka are exceeding fifty percent of the solar PV over the transformer capacity, which shed a green light to assess the cumulative effect of the rooftop solar PVs. In this study, a distribution feeder with high solar PV penetration has been selected and power quality issues such as harmonics, over voltage and DC injection are analyzed under various conditions. Effects of nonlinear loads were also assessed to create an accurate representation of the existing network. The simulation results identify whether the selected system satisfies the statutory limits imposed by various global regulations concerned with power quality.31931 00 ©2019 IEEE Power Quality Issues Due to High Penetration o.
Trang 1Power Quality Issues Due to High Penetration of Rooftop Solar PV in Low Voltage Distribution
Networks: A Case Study
H H H De Silva
Department of Electrical Engineering,
University of Moratuwa, Sri Lanka
ORCID:
https://orcid.org/0000-0002-4359-1643
D K J S Jayamaha Department of Electrical Engineering, University of Moratuwa, Sri Lanka ORCID:
https://orcid.org/0000-0002-6803-8107
N W A Lidula Department of Electrical Engineering, University of Moratuwa, Sri Lanka ORCID:
https://orcid.org/0000-0003-3556-4693 AbstractIncreased penetration of rooftop solar PV is
causing undesirable technical impacts on the distribution
networks Several urban distribution transformers in Sri
Lanka are exceeding fifty percent of the solar PV over the
transformer capacity, which shed a green light to assess the
cumulative effect of the rooftop solar PVs In this study, a
distribution feeder with high solar PV penetration has been
selected and power quality issues such as harmonics, over
voltage and DC injection are analyzed under various
conditions Effects of non-linear loads were also assessed to
create an accurate representation of the existing network The
simulation results identify whether the selected system satisfies
the statutory limits imposed by various global regulations
concerned with power quality
Keywords DC Injection, harmonics, low voltage network,
over voltage, power quality, rooftop solar PV
I INTRODUCTION With the popularity of the national promotional projects
for roof-top solar PV in Sri Lanka, electricity consumers
showed a tendency of increased installation of roof-top solar
PVs Ceylon Electricity Board (CEB), the electrical power
generation, transmission and distribution authority of Sri
Lanka has published that 70 MW of rooftop solar were
installed by the end of 2017 [1] However, unplanned
interconnection of distributed generators (DGs) could lead to
technical impacts on power system reliability, power quality
and stability
Particularly, power quality issues arising from increased
integration of solar PVs to the utility grid have gained
significant research attention The power electronic converter
that interfaces the solar PV to the system is the main factor
that affects the power quality of the utility network
Thyristor-based, line-commutated inverters are considered
undesirable on the power system due to the generated
harmonic currents [2] To achieve better control and to
address the harmonic issue, the inverter technology evolved
to pulse width modulation (PWM) technology, which
resulted in a better interface system to the solar PV [2] Once
a roof-top solar PV system is installed, it will be
commissioned if and only if all the system parameters are
within statutory limits imposed by the standards such as [3]
and [4] However, cumulative effects are not particularly
evaluated at the commissioning level and therefore, the
impact of increased integration of rooftop solar PV to the
local network is found a timely necessity and has been
evaluated by several research studies
In distribution level, power quality issues in literature
mainly focus on voltage issue In many such studies, PV
inverters are modeled as constant PQ sources, which is
sufficient for analyzing the voltage profile [5-7] In [8], detailed modelling of the PV system is used to analyze the voltage levels and losses along the feeder Futuristic analysis based on a stochastic approach to increase the solar penetration levels is also covered in [8-10] However, the studies reveal that voltage levels have not exceeded the statutory limits due to the existing solar PV penetration levels [6,8,9,11,12] In harmonic analysis related to distribution networks, total voltage harmonic distortion (VTHD) and total current harmonic distortion (ITHD) are observed under different conditions in [13,14] The aggregated effect of multiple single phase inverters and three phase inverters has been analyzed separately in [15] However, according to [11] and [14], with the considered solar PV penetration levels, recorded VTHD levels were within the statutory limits while ITHD levels were violated
in many cases Several studies have considered solar PV as the main or only means of harmonics injection, while the effects of non-linear loads being omitted [9-14] In studies, which assess the harmonic injection by multiple solar PV inverters, a finite pattern on harmonics is not quite observable due to the primary and secondary emissions of the solar PV inverters [13] The resultant harmonics on the system may either attenuate or enhance the individual harmonic content
In this paper, both solar PV and non-linear loads are modeled in detail to replicate the accurate picture of the distribution feeder In analyzing current harmonics at the system level, total demand distortion (TDD) is preferred over ITHD [2] and used in this paper in contrast to other studies [5-8,10-14] Total demand provides a common reference for measuring current distortion compared to the fundamental current component DC injection is equally important due to its impact on the transformers [16,17] However, DC injection due to solar PV has not been recognized in the reported power quality studies, despite its position in regulatory standards [4, 16] The paper is organized as follows In Section II, power quality issues due to increased rooftop solar PV and the limitations are presented In Section III, the details of the modeled network are presented Section
IV presents the results of the study and a qualitative analysis
on the results The effects of solar irradiance and loading condition are the main variables and are presented under six different cases Finally, section V draws the conclusion
II POWER QUALITY ISSUES DUE TO INCREASED SOLAR
PVINTEGRATION The power quality issues associated with solar PV co-relates with the intermittent nature of the PV generation and the effects from the power electronics interface Possible
Trang 2power quality issues and their causes related to solar PV are
listed in Table I [10]
A Harmonic Limitation Requirements and Standards
THD
The THD definition in (1) is derived from IEEE 519
standard [3] where, Mh is the RMS value of the hth harmonic
component of the quantity M, which can be either voltage or
current [2,3], and M1 is the fundamental value of the quantity
M concerned In a system-level study, TDD is more
appropriate to evaluate the effect of current harmonics at
varying load conditions [2] It is a general practice to check
the current harmonic levels with the base as the inverter rated
current, which is known as total rated distortion (TRD) [18]
However, this study employs maximum demand for the
feeder at considered cases as the base to calculate the TDD
In the TDD definition given in equation (2), Ih is the hth
harmonic current and IL is the maximum demand current at
the PCC
As defined in IEEE 519 standard, the recommended
limits for LV VTHD and TDD are given in Table II As per
the guidelines in [3], since the PV inverter falls into the
power generation equipment category, the TDD limits are
considered from the category Isc/IL<20, hence the
requirements as in Table II Isc is the maximum short circuit
current at the PCC
TABLE I P OWER Q UALITY I SSUES R ELATED TO S OLAR PV
Flicker Variations of the solar PV generation [5]
Slow voltage
variations Power flow variations Apparent motion of the position of the sun, change in
cloud cover, Shading effects
Fast voltage
variations
High capacity solar PV
Tracking systems
Intermittency of the power generation due to change in
cloud cover, climatic conditions
Variations in the reactive power [10]
Over- voltage Solar generation (or any DG) increases voltage at
terminals of the generator
Voltage
Unbalance Uneven interconnection of single phase inverters
Low order
harmonics
Harmonic network impedance affected by solar PV
inverters [10]
Primary emissions determined by the control algorithm
of the inverter
Secondary harmonics caused by the background
distortion and the input impedance of the inverter [10]
Supra
harmonics Residues from the switching in inverters Connection, disconnection of neighbouring sources
impact on primary emissions
Neighbouring harmonic sources causes secondary
emissions [10]
DC offset Inverters are sources of DC injection [17]
TABLE II H ARMONIC L EVELS [3]
TDD 3 h 11 11 h 17 17 h 23 23 h 35 23 h 35
For the harmonic measurements, standards do not specify whether line-line or line-neutral currents/voltages to be used Based on vectorial analysis, line-line harmonic voltages could range between 0 to 1.15 times measured between line-neutral harmonic voltages at a given frequency These two extreme cases correspond to an angle between two vectors of 0º and 180º respectively [19] However, field measurements
at typical LV distribution sites show that these extreme cases are not observed and the harmonic currents/voltages measured in line-line are very similar to those measured in line-ground Hence in this study, line - ground voltages/ currents are chosen for the harmonic analysis The harmonic current limits indicate the minimum quality of current waveform the customer can inject into the grid at the PCC
At the same time, the utility is responsible for providing a clean low distorted voltage to the customer In addition to harmonic distortion it is worthwhile to analyze the other power quality requirements related to solar PV integration
B Other Power Quality Requirements and Standards Over Voltage: The LV standards specify a ± 6% of the nominal voltage to be maintained [20,21] Specifically, for DG, temporary over voltage (TOV) limits are specified in [4] to be maintained at the PCC However, this study will not focus on the TOV limits, but will consider the 6% threshold
DC Injection: According to IEEE 929-2000, the PV system shall not inject DC current greater than 0.5% of the rated inverter current into the utility interface under any operating condition [22] This limit is highly country-specific, unlike the harmonic limits Some countries have imposed an absolute current as the maximum limit; for example, Australian standards specify a limit of 5 mA as the maximum permitted DC injection, and in Germany it is 1 A [23] The maximum allowable limit in Sri Lanka at the inverter PCC is 1% [21] In this study, a representation of the absolute current at the system is presented High DC injection to the grid is harmful due to possible saturation of the transformer
Voltage Unbalance: The unbalance voltage under operating conditions for a period of 1 week of the 10-minute RMS value of the negative sequence voltage unbalance factor (VUBF) shall be 2% A VUBF of 3%
is allowed occasionally [24]
Flicker: For LV distribution systems, the compatibility levels for flicker absolute short term - Pst and long-term flicker - Plt indices are 1 and 0.8 respectively [4,25] In [26], flicker measurements for 3.5 kW grid connected inverters have not displayed any violations Assessing the flicker levels in high capacity inverters might be a good future study as the low capacity inverter would not cause any significant voltage variation if the grid is sufficiently stiff
III MODELLING THE NETWORK High solar PV penetrated feeder (68% penetration from the maximum demand) of Lanka Electricity Company (LECO, one of the distribution level authorities) network is selected for the study The network is modeled in MATLAB/SIMULINK, and smart meter data recorded in May 2018 are used in the model The details of the feeder are shown in Table III
Trang 3TABLE III N ETWORK D ETAILS
Transformer 250 kVA 11 kV/400 V
Present maximum
demand
192 kVA / 352 customers Conductor type ABC : 3x70 mm 2 + 54 mm 2
R = 0.443 /km , X = 0.26 mH/km Selected feeder No 2 from 3 feeders /82 customers
Feeder length 400m
Maximum feeder
demand
70 kVA (67 kW+ 21 kVar) Solar customers 9 (48 kW)
A Solar PV Modelling
Detailed single phase and three phase solar PV systems
were developed in MATLAB/ SIMULINK representing the
Yingli Solar (China) YL260p-35b A study conducted on
the solar assessment in Sri Lanka has shown that the
maximum irradiance can reach up to 1000 Wm-2 [27]
Therefore, considering the hourly insolation variation, three
scenarios are considered:
1 100% irradiance at daytime (1000 Wm-2)
2 50% irradiance at daytime due to shading effects
(500 Wm-22)
3 0% irradiance at nighttime
Temperature was kept constant throughout the
simulation at 40 ºC
B InverterModelling
Both 3 phase and single-phase solar PV inverters were
employed in the simulation Single phase inverters are of 3
kW, 5kW capacities and the three phase inverters are of 6
kW, 10 kW capacities The inverter is modeled as a detailed
switching model to create an accurate model of the system
Single phase Inverter model:
Single phase full bridge IGBT inverter
2 level Unipolar PWM generator 20 kHz
MPPT Tracking Perturb and observe algorithm
Active power controller: single phase dq current control
Double loop PWM controlling
Three phase Inverter model:
3 phase universal bridge with IGBT/ Diode
DC boost converter (350- 700 VDC)
DC link pulse generator 5 kHz
Double loop PWM controlling
Active power controlling: dq current control
C Load Modelling
Energy consumption at each pole of the selected feeder is
taken for the calculation of loads Data is collected in every
15-minute period and the average load consumed at each
pole during different times in the day is considered based on
the load curve of SL Three-time ranges in the load profile
were selected based on the demand as (i) 12 am to 4 am (ii)
10 am to 4 pm (iii) 6 pm to 10 pm Since the effect of solar
penetration has to be studied, two different loadings: as high
loading (above 90 % of the maximum feeder loading) and
low loading (below 30 % of the maximum feeder loading)
were considered in the daytime The load variations along
the feeder are shown in Fig 1 The poles of the feeder were
reduced using the full feeder reduction method in [28] The
feeder was reduced to 13 poles as shown in Fig 2 and,
different scenarios simulated are shown in Fig 3 Scenario 1
Fig 1 Feeder loading at 4 different times considered
Fig 2 Modeled network in MATLAB/ SIMULINK
Fig 3 Scenarios and cases considered in this study considers 100% linear loads while Scenario 2 considering 50% of the loads to be non-linear
Non-linear loads such as computers, fluorescent lamps, induction motors with variable speed drives (VSDs) and the recent trends of using inverter-based motors and compressors
in domestic appliances like air conditioners, refrigerators, and the washing machines are also major concerns on the power quality of the distribution network According to [29]
up to 69% of the modern domestic load may now be comprised of non-linear loads Due to the unavailability of data for the penetration level of non-linear loads in the considered network, 50% of loads are considered to be non-linear, and modeled accordingly A resistive load is connected across a diode bridge to mimic the non-linear load [30].
D Measurements The fast Fourier transform (FFT) analyzer in MATLAB was used for the harmonic calculations The THD, DC, offset, I1 were directly obtained from the simulation TDD is defined as in equation (3) and the THD value was obtained from the FFT analyzer in MATLAB [31] Here, I1 is the fundamental current and IL is the peak demand current At
Trang 4each case, peak current measured for over 30 minutes was
considered as the IL
(3)
The single phase loads and the single phase solar PV
generation are located in random phases of each pole
replicating the unplanned connections This adds a voltage
unbalance to the system Hence, the maximum demand
current at any given phase is considered and, the maximum
demand currents for the Cases 01-06 are 31 A, 86 A, 86 A,
28 A, 28 A and 96 A respectively
IV RESULTS AND DISCUSSION
As the first step, the THD and TDD levels at the metering
PCC of each inverter were measured and noted that the
levels were within the accepted limits [3] However, the
scope of this study is to analyze the system-level impacts
Therefore, when each inverter is operated alone, the THD
and TDD levels at the corresponding pole were measured
and presented in Table IV It can be observed from Table IV,
that the highest harmonic distortion levels are due to the
three phase inverters The three phase inverters do not
generate triplen harmonics under balance loading [2] and, a
rise of THD levels by single phase inverters compared to the
three phase inverters is expected However, due to the
three-phase unbalanced loads, the effect of triplens will be
significant [33] It can also be noted that the 3 kW single
phase inverter has significant distortion levels compared to 5
kW single phase inverters Lower the power rating of an
inverter, higher distortion level is caused to the power
system [33,34] When system-level impact of individual
inverters is considered, they present VTHD variation of 0%
- 0.39% and ITHD variation of 0.01% - 0.82% and the DC
offset ranges from 0% - 0.06%
When the cumulative effect is considered, with the
presence of multiple harmonic generation sources, the
resultant harmonic levels might either attenuate or enhance
[2,15,32]
A Voltage Variation Along the Feeder
To analyze the voltage variation along the feeder, the
transformer secondary voltage was set to 235 V according to
the measurement data obtained As shown in Fig 4, under
the existing conditions, no voltage violation is observed in
this selected feeder having 68% solar PV penetration
Voltage variation along the Feeder under Scenario 1 (in
Fig 3 - 100% linear loads) is presented in Fig 4(a) and
same under Scenario 2 (in Fig 3 - 50% non-linear loads) is
presented in Fig 4(b) A similar variation is observable
under both scenarios
According to Fig 4(a) and (b), voltages have risen at the
poles having solar PV connected lines when there is solar
generation This agrees with the observations in [10], and is
observable, when comparing Cases 01 and 06 (no solar
generation) with Cases 02 05 (having the solar
generation) Typical voltage drop along the line due to the
conductor impedance can be observed in Cases 01 and 06
In the Cases 02 05, specially under high solar generation,
voltage rise is observable up to pole 8, where the solar PV
connection terminates Then, the voltage drops along the
line due to the line losses A higher increase in voltage
compared to the other cases is observable in Case 04, where
TABLE IV M AXIMUM L EVELS O F P OWER Q UALITY I NDICATORS
W HEN E ACH I NVERTER IS O PERATED A LONE
Config 1ph 1ph 1ph 3ph 1ph 3ph 3ph 1ph VTHD % 0 0.09 0 0.39 0 0.39 0.33 0.06 TDD% 0.01 0.07 0.01 0.13 0.01 0.13 0.82 0.46
DC (%) 9e-4 0.053 0.003 0.04 0.002 0.04 0.06 0.04
Fig 4 Voltage variation along the Feeder (a) Scenario 1, (b) Scenario 2
Fig 5 VTHD along the Feeder (a) Scenario 1, (b) Scenario 2
there is maximum solar irradiance with low load demand If the PV generation exceeds, in feeder loads as can be observed in Case 04, power flows back from feeder to the upstream network which causes the voltage rise [35] In this case maximum of 4 V voltage rise is observed at pole 8
B Voltage Total Harmonic Distortion- VTHD
It is observed that the VTHD does not exceed the limit
of 8% as indicated in Table 2 However, individual harmonic levels might exceed the limits, but were not analyzed in this study
When the individual inverter operation is compared against all the inverters in operation significant voltage distortion is expected Analyzing the effect of multiple inverters on system power quality is a complex study
Trang 5because, many factors, such as inverter control, location of
the inverter and the strength of the grid could contribute
Even though a cumulative effect is expected, in some
instances the harmonics can also be attenuated due to the
secondary emissions For low order harmonics, the multiple
inverters might increase the harmonic levels if the grid is
weak [32] Having all the solar inverters being connected,
the VTHD along the Feeder under Scenario 1 and Scenario
2 (in Fig 3) are presented in Fig 5 (a) and (b) respectively
The VTHD levels have significantly increased when
non-linear loads in the system are considered As clean
undistorted voltage waveform supplied at the transformer by
the utility is unlikely to get distorted at its LV side, under
both scenarios, the voltage distortion at the end of the feeder
is comparatively higher than the transformer LV side
In Scenario 1, maximum recorded THD is 0.9 % and in
the Cases 01 and 06, the THD is zero due to the absence of
solar PV generation The impact of solar irradiance level on
the THD can also be observed in Fig 5(a) At all the poles,
given a 50% increase of irradiance, the THD has a slight
increase of around 0.1 - 0.5% This is also verified by the
study done in [36], which states 1.5% - 2.2% change of
THD for instantaneous fluctuations of irradiance However,
this study has focused only on a step change of irradiance
and the THD is considered only at the steady state in
accordance with the definition of THD [2] The rise of
VTHD at the feeder end is significant in low loading
conditions with high PV generation (Case 04) under
Scenario 1 (case with 100% linear loads)
As can be seen in Fig 5(b), under Scenario 2 (case with
50% non-linear loads), VTHD levels have significantly
increased in high loading conditions with high PV
generation (Case 02) However, the results do not reveal a
clear relation between the VTHD and the loading condition
and PV generation under Scenario 2, due to the effects of
non-linear loads
C Total Demand Distortion -TDD
The variation of TDD under scenario 1 and 2 along the
feeder are shown in the Fig 6 (a) and (b) respectively
Unlike in voltage variation and VTHD levels, TDD in both
scenarios is insignificant or marginal to the end of the feeder
from the Pole 6, but TDD limits are violated up to the pole 5
from the transformer [3] This is in the agreement with the
general tendency of harmonic current flow, which is from
harmonic source towards the transformer [2] As in Fig
6(a), under scenario 1, at pole 3, TDD is observed to be
18.8% The higher solar penetration at pole 4 has increased
the TDD at the pole 3
Although it is expected the high irradiance to lower the
current harmonics [36], it is not observed in this study The
two irradiance variation levels (50% and 100%) considered
are not sufficient to represent this fact In [36] a clear ITHD
variation can be observed when the irradiance levels are
changed from 10% - 50% In Scenario 2, in the night peak
(Case 06) higher current distortion is observed indicating the
distortion levels by the non-linear loads In the transformer
end it is high as 19% and at the feeder-end it is around 3%,
which is still higher compared to the other cases The
harmonic current towards the transformer LV side can be
clearly observed in the Scenario 2 (Fig 6(b)) as well
Individual harmonic evaluation must be carried out for a
better representation of the harmonic propagation
Fig 6 TDD along the Feeder (a) Scenario 1, (b) Scenario 2
Fig 7 DC Injection along the Feeder (a) Scenario 1, (b) Scenario 2
D DC Offset The study of DC current injection is important due to the following facts [2,11]: (i) the flow of harmonic currents is towards the transformer, and (ii) DC current can lead to transformer core saturation The allowable limit of DC current injection is 0.5% at the PCC of the inverter [22] However, in this study, the absolute DC offset at the poles are presented
The DC injection along the feeder under Scenarios 1 and
2 are shown in Fig 7 (a) and (b) respectively In Fig 7 (a), a
DC offset of more than 0.1 A is observed upto pole 7, which
is highly undesirable For example, at the inverter PCC (5
kW, 1 phase) a 0.5 A of DC offset will create a DC injection
of 2.3% The effect of high solar irradiance has affected the rise of DC offset irrespective of the load non-linearity At the feeder end, the DC current is low due to absence of solar
PV at the end of feeder
V CONCLUSION This paper has presented a quantitative analysis of power quality issues arising with high penetration of rooftop solar
PV in the low voltage distribution network A case study was carried out for a selected distribution feeder with 68%
of rooftop solar PV penetration The system was developed with detailed three phase and single phase inverter models, linear and non-linear loads, to represent the existing system The voltage variation, THD, TDD, and DC offset along the feeder are the power quality indicators used to analyze the
Trang 6system-level impact introduced with the high solar PV
penetration The effects on the power quality indicators
under varying conditions; irradiance level, loading level and
the time of the day are discussed
Although, THD and DC injection levels do not violate
the statutory limits, the voltages towards the end of the
feeder are marginal under the present solar PV penetration
level of 68% The TDD values exceed the specified limits at
several cases considered in this study Furthermore, all the
power quality indicators present a significant increase when
the system is equipped with non-linear loads, indicating
negative impacts on the system
The cumulative effect on the system power quality by
the non-linear loads, which constitutes a considerable
percentage in the domestic network, has to be assessed in
detail In addition, the effect of increased rooftop-top solar
PV on system power quality in the upstream system, i.e the
MV side of the transformer, requires further investigation
ACKNOWLEDGMENT Authors would like to acknowledge the financial support
provided by the University of Moratuwa, Sri Lanka under
the research grant SRC/CAP/2018/1
REFERENCES
[1] CEB, "Statistical digest," 2017 [Online] Available:
https://www.ceb.lk/publication-media/statistical-reports/74/en [Accessed
June 2019]
[2] R Dugan, M F Mcgranaghan, S Santose and H Beaty, Electrical
power systems quality, 2, Ed., McGraw-Hill, 2008
[3] IEEE 519-2014, IEEE recommended practise- the limits, IEEE Power
and Energy Society, 2014
[4] IEEE Std 1547-2003, IEEE Standard for interconnecting distributed
resources with electric power systems., 2003
[5] S Eftekharnejad, V Vittal, G T Heydt, B Keel, and J Loehr, "Impact
of increased penetration of photovoltaic generation on power systems,"
IEEE Transactions on Power Systems, vol 28, no 2, pp 893 - 901, 2013
[6] J Watson, N R Watson, D Martin, A R Wood and S Lemon,
"Impact of solar photovoltaics on the low voltage distribution network in
New Zealand," IET Generation, Transmission and Distribution, pp 1-9,
2016
[7] R Tonkoski, D Turcotte, T El-Fouly , "Impact of high pv penetration
on voltage profiles in residential neighbourhoods," IEEE Transactions on
Sustainable Energy, vol 3, no 3, pp 518 - 527, 2012
[8] D Chathurangi, U Jayatunga, M Rathnayake, A Wickramasinghe, A
Agalgaonkar, and S Perera, "Potential power quality impacts on LV
distribution networks with high penetration levels of solar PV," in
International Conference on Harmonics and Quality of Power, Slovenia,
2018
[9] D Almeida, A Abeysinghe and J B Ekanayake, "Analysis of rooftop
solar impacts on distribution networks," Ceylon Journal of Science, vol 48,
no 2, March 2019
[10] J Smith, S Rönnberg, M Bollen, J Meyer, and M Blanco, "Power
quality aspects of solar power results from CIGRE JWG C4/C6.29," in
International Conference & Exhibition on Electricity Distribution (CIRED),
2017
[11] Potential technical impacts of rooftop solar generation [Online]
Available:
https://www.adb.org/sites/default/files/linked-documents/50373-002-sd-03.pdf [Accessed: 10-Aug-2019]
[12] J Urbanetz, P Braun and R Rüther, "Power quality analysis of
grid-connected solar photovoltaic generators in Brazil," Energy conversion and
management, vol 64, pp 8-14, 2012
[13] J Niitsoo, M Jarkovoi, P Taklaja, J Klüss and I Palu, "Power quality
issues concerning photovoltaic generation in distribution grids," Smart Grid
and Renewable Energy, pp 148-163, 2015
[14] M A Awadallah, B Venkatesh and B N Singh, "Impact of solar
panels on power quality of distribution networks and transformers,"
Canadian Journal of Electrical and Computer Engineering , vol 38, no 1.,
2015 [15] D Infield, P Onions, A D Simmons and G A Smith, "Power quality from multiple grid-connected single-phase inverters," IEEE Transactions on Power Delivery, vol 19, no 4, pp 1983 - 1989, 2004
[16] L Gertmar, P Karlsson and O Samuelsson, "On DC injection to ac grids from distributed generation," in European Conference on Power Electronics and Applications, 2005
[17] V Salas, E Olías, M Alonso, F Chenlo and a A Barrado, "DC current injection into the network from PV grid inverters," in Photovoltaic Energy Conversion, 2006
[18] S Vlahinic, D Brnobic and N Stojkovic, "Indices for harmonic distortion monitoring of power distribution systems," IEEE Transactions on Instrumentation and Measurement, vol 58, no 5, pp 1771 - 1777, 2009 [19] J P Braun, V Gosbell and S Perera, Possible measurement errors in relation to harmonics and flicker - UOW. [Online] Available: https://www.elec.uow.edu.au/apqrc/content/papers/AUPEC/AUPEC03_6.pd
f [Accessed: 10-Aug-2019]
[20] IEC 60038:2002, IEC standard voltages, 2002
[21] Public Utility Commission of Sri Lanka, Distribution Code of Sri Lanka, 2012 [Online] Available: https://www.ceb.lk/front_img/img_ reports/1532500020Distribution_Code.pdf [Accessed: 10-Aug-2019] [22] IEEE 929-2000, IEEE recommended practice for utility interface of photovoltaic (PV) systems,2000, April
[23] V Salasa, E Ol´asa, M Alonsob and F Chenlo, "Overview of the legislation of dc injection in the network for low voltage small grid-connected pv systems in Spain and other countries," Renewable and Sustainable Energy reviews, vol 12, p 575583, 2008
[24] BS EN 50160: 2000, Voltage characteristics of electricity supplied by public distribution systems, 2000
[25] IEC 61000.3.7.2012, EMC Limits- Assessment of emission limits for the connection of fluctuating installations to MV, HV, and EHV power systems, 2012
[26] D Perera, P Ciufo, L Meegahapola, and S Perera, Power quality emission assessment of photovoltaic inverters based on IEC Technical Report 61000-3-15:2011, 2013 Australasian Universities Power Engineering Conference (AUPEC), 2013
[27] Technical Assistance Consultants Report Final Report . [Online] Available: https://www.adb.org/sites/default/files/project-document/151003/43576-012-tacr-03.pdf [Accessed: 10-Aug-2019] [28] M J Reno, R Broderick and S Grijalva, "Sandia Formulating a Simplified Equivalent Representation of Distribution Circuits for PV Impact Studies," 2013
[29] Electrifying Sydney: 100 years of Energy Australia, Energy Australia, 11-Nov-2018 [Online] Available:
https://www.worldcat.org/title/electrifying-sydney-100-years-of-energyaustralia/oclc/61460770 [Accessed: 11-Aug-2019]
[30] C Venkatesh, D S Kumar and D Sarma, "Modelling of nonlinear loads and estimation of harmonics in industrial distribution system," in Fifteenth National Power Systems Conference, Bombay, 2008
[31] M P Donsion and M I Buzdugan, Power Quality, Cambridge Scolars Publishing, 2017
[32] Department of Trade and Industry- Halcrow Gilbert Associates Ltd.,
"Co-ordinated experimental research into power interaction with the supply network Phase 1 ETSU S/P2/00233/REP," 1999
[33] M Saçla, O Ayana, M Silsüpüra and B E Türkay, "Power quality comparison of single-phase and three-phase inverter topologies for renewable energy systems," International Journal of Smart Grid and Clean Energy, vol 8, no 2, pp 174-183, 2019
[34] M A Abellaa, F Chenloa and V Salas, "Test results of PV grid connected inverters," [Online] Available: https://www.researchgate.net/publication/276262790_Test_results_of_PV_g rid_connected_inverters [Accessed: 10-Aug-2019]
[35] M Alam, K Muttaqi and D Sutanto, "Distributed energy storage mitigation of Voltage-Rise impact caused by rooftop solar PV," IEEE Power and Energy Society General Meeting, July 2012
[36] M Patsalides, D Evagorou and G Makrides, "The Effect of solar irradiance on the power quality behaviour of grid connected photovoltaic systems"