Air flow rate for cooling Power dissipation of AC motor drive Flow Rate cfm Flow Rate m3/hr Power Dissipation Model No.. Air flow rate for cooling Power dissipation of AC motor drive Fl

Trang 1

1688 Jiangxing East Road,

Wujiang Economic Development Zone

Wujiang City, Jiang Su Province,

People's Republic of China (Post code: 215200)

TEL: 86-512-6340-3008 / FAX: 86-769-6340-7290

Delta Greentech (China) Co., Ltd.

238 Min-Xia Road, Cao-Lu Industry Zone,Pudong, Shanghai,

People's Republic of China

Delta Electronics (Korea), Inc.

234-9, Duck Soo Building 7F, Nonhyun-Dong,

Kangnam-Gu, Seoul, Korea 135-010

TEL: 82-2-515-5305 / FAX: 82-2-515-5302

Delta Electronics Int’l (S) Pte Ltd

4 Kaki Bukit Ave 1, #05-05, Singapore 417939

TEL: 65-6747-5155 / FAX: 65-6744-9228

Delta Electronics (India) Pvt Ltd.

Plot No 43, Sector – 35, HSIIDC,

Gurgaon122001, Haryana, India

TEL: 1-919-767-3800 / FAX: 91-124-403-6045

Americas

Delta Products Corporation (USA)

Raleigh Office

P.O Box 12173,5101 Davis Drive,

Research Triangle Park, NC 27709, U.S.A.

TEL: 1-919-767-3800 / FAX: 1-919-767-8080

Delta Greentech (Brasil) S.A

Sao Paulo Office

Rua Itapeva, 26-30 Andar Edificio Itapeva One-Bela Vista

CH2000 Series User Manual

Delta Heavy Load Application Field Oriented Control Drive

Trang 2

D ANGER

is made

 Even if the power has been turned off, a charge may still remain in the DC-link capacitors with hazardous voltages before the POWER LED is OFF Please do not touch the internal circuit and components

 There are highly sensitive MOS components on the printed circuit boards These components are especially sensitive to static electricity Please do not touch these components or the circuit boards before taking anti-static measures Never reassemble internal components or wiring

 Ground the AC motor drive using the ground terminal The grounding method must comply with the laws of the country where the AC motor drive is to be installed

 DO NOT install the AC motor drive in a place subjected to high temperature, direct sunlight and inflammables

NOTE

The content of this manual may be revised without prior notice Please consult our distributors or download the most updated version at http://www.delta.com.tw/industrialautomation

Trang 3

CHAPTER 1 INTRODUCTION 1-1 CHAPTER 2 INSTALLATION 2-1 CHAPTER 3 UNPACKING 3-1 CHAPTER 4 WIRING 4-1 CHAPTER 5 MAIN CIRCUIT TERMINALS 5-1 CHPATER 6 CONTROL TERMINALS 6-1 CHAPTER 7 OPTIONAL ACCESSORIES 7-1 CHAPTER 8 OPTION CARDS 8-1 CHAPTER 9 SPECIFICATION 9-1 CHAPTER 10 DIGITAL KEYPAD 10-1 CHAPTER 11 SUMMARPY OF PARAMETERS 11-1 CHPAPTER 12 DESCRIPTION OF PARAMETER SETTINGS 12-1 CHAPTER 13 WARNING CODES 13-1 CHAPTER 14 FAULT CODES AND DESCRIPTIONS 14-1 CHAPTER 15 CANOPEN OVERVIEW 15-1 CHAPTER 16 PLC FUNCTION 16-1 CHAPTER 17 HOW TO SELECT THE RIGHT AC MOTOR DIRVE 17-1 CHAPTER 18 SUGGESTIONS AND ERROR CORRECTIONS FOR STANDARD AC MOTOR DRIVES 18-1 CHAPTER 19 APPLICATION OF CH2000……… ……… 19-1

Application Control BD V1.00;

Keypad V1.01;

Trang 4

Chapter 1 Introduction

Receiving and Inspection

After receiving the AC motor drive, please check for the following:

1 Please inspect the unit after unpacking to assure it was not damaged during shipment Make sure that the part number printed on the package corresponds with the part number indicated on the nameplate

2 Make sure that the voltage for the wiring lie within the range as indicated on the nameplate Please install the AC motor drive according to this manual

3 Before applying the power, please make sure that all the devices, including power, motor, control board and digital keypad, are connected correctly

4 When wiring the AC motor drive, please make sure that the wiring of input terminals “R/L1, S/L2, T/L3” and output terminals”U/T1, V/T2, W/T3” are correct to prevent drive damage

5 When power is applied, select the language and set parameter groups via the digital keypad

(KPC-CC01) When executes trial run, please begin with a low speed and then gradually increases the speed untill the desired speed is reached

Nameplate Information

Trang 5

Model Name

Serial Number

Trang 6

RFI Jumper

RFI Jumper: The AC motor drive may emit the electrical noise The RFI jumper is used to suppress the interference (Radio Frequency Interference) on the power line

Frame A~C

Screw Torque: 8~10kg-cm(6.9-8.7 lb -in.)

Loosen the screws and remove the MOV-PLATE Fasten the screws back to the original position after MOV-PLATE is removed

Trang 7

Frame D~H

Remove the MOV-PLATE by hands, no screws need to be loosen

Main power isolated from earth:

If the AC motor drive is supplied from an isolated power (IT power), the RFI jumper must be cut off Then the RFI capacities (filter capacitors) will be disconnected from ground to prevent circuit damage

(according to IEC 61800-3) and reduce earth leakage current

CAUTION!

1 When power is applied to the AC motor drive, do not cut off the RFI jumper

2 Make sure main power is switched off before cutting the RFI jumper

3 The gap discharge may occur when the transient voltage is higher than 1,000V Besides,

electro-magnetic compatibility of the AC motor drives will be lower after cutting the RFI jumper

4 Do NOT cut the RFI jumper when main power is connected to earth

5 The RFI jumper cannot be cut when Hi-pot tests are performed The mains power and motor must be separated if high voltage test is performed and the leakage currents are too high

6 To prevent drive damage, the RFI jumper connected to ground shall be cut off if the AC motor drive is installed on an ungrounded power system or a high resistance-grounded (over 30 ohms) power system or a corner grounded TN system

Trang 8

Frame A

VFD007CH23A-21, VFD015CH23A-21, VFD022CH23A-21, VFD037CH23A-21

VFD007CH43A-21, VFD015CH43A-21, VFD022CH43A-21, VFD037CH43A-21, VFD055CH43A-21 VFD007CH4EA-21,VFD015CH4EA-21, VFD022CH4EA-21, VFD037CH4EA-21, VFD055CH4EA-21

Unit: mm [inch]

130.0 250.0 170.0 116.0 236.0 45.8 6.2 22.2 34.0 28.0

Trang 9

Frame B

VFD055CH23A-21,VFD075CH23A-21,VFD110CH23A-21,

VFD075CH43A-21,VFD110CH43A-21, VFD150CH43A-21,

VFD075CH4EA-21,VFD110CH4EA-21,VFD150CH4EA-21,

Detail A (Mounting Hole)

Detail B (Mounting Hole)

190.0 [7.48]

173.0 [6.81]

303.0 [11.93]

77.9 [3.07]

8.5 [0.33]

22.2 [0.87]

34.0 [1.34]

28.0 [1.10]

D1*: Flange mounting

Trang 10

Frame C

VFD150CH23A-21,VFD185CH23A-21

VFD185CH43A-21, VFD220CH43A-21,VFD300CH43A-21

VFD185CH4EA-21,VFD220CH4EA-21,VFD300CH4EA-21

Detail A (Mounting Hole)

Detail B (Mounting Hole)

See Detail A

See Detail B

Unit: mm [inch]

Trang 11

Frame D

D1:

VFD220CH23A-00, VFD300CH23A-00, VFD370CH23A-00

VFD370CH43A-00, VFD450CH43A-00, VFD550CH43A-00, VFD750CH43A-00,

W W1

S1 S1

SEE DETAIL A

DETAIL A (MOUNTING HOLE)

DETAIL B (MOUNTING HOLE) SEE DETAIL B

D

D1

S2 D2

285.0 [11.22]

550.0 [21.65]

525.0[20.67]

492.0[19.37]

107.2[4.22]

16.0[0.63]

11.0[0.43]

18.0

Trang 12

D2:

VFD220CH23A-21, VFD300CH23A-21,VFD370CH23A-21

VFD370CH43A-21, VFD450CH43A-21,VFD550CH43A-21, VFD750CH43A-21

W W1

1

2 3

S1 S1

SEE DETAIL A

DETAIL A (MOUNTING HOLE)

DETAIL B (MOUNTING HOLE)

275.0 [10.83]

285.0 [11.22]

550.0 [21.65]

525.0 [20.67]

492.0 [19.37]

107.2 [4.22]

16.0 [0.63]

11.0 [0.43]

18.0 [0.71]

76.2 [3.00]

34.0 [1.34]

22.0 [0.87]

Trang 13

Frame E

E1: VFD450CH23A-00, VFD550CH23A-00, VFD900CH43A-00, VFD1100CH43A-00

W1 W

D1 D

335.0 [13.19

589 [23.19]

560.0[22.05]

528.0[20.80]

143.0[5.63]

18.0[0.71]

13.0[0.51]

18.0 [0.71]

- - -

D1*: Flange mounting

Trang 14

Frame E

E2: VFD450CH23A-21, VFD550CH23A-21, VFD900CH43A-21, VFD1100CH43A-21

W1 W

D1 D

300.0[11.81]

335.0 [13.19

589 [23.19]

560.0[22.05]

528.0[20.80]

143.0[5.63]

18.0[0.71]

13.0[0.51]

18.0 [0.71]

22.0 [0.87]

34.0[1.34]

92.0[3.62]

D1*: Flange mounting

Trang 15

See Detail A

See Detail B

Detail A (Mounting Hole)

Detail B (Mounting Hole)

D2

D D1

Trang 16

W W1

D D1

1

See Detail A

See Detail B

Detail A (Mounting Hole)

Detail B (Mounting Hole)

Trang 17

Frame G

G1: VFD1600CH43A-00, VFD1850CH43A-00, VFD2200CH43A-00

W1 W

Trang 18

Frame G

G2: VFD1600CH43A-21, VFD1850CH43A-21, VFD2200CH43A-21

W1 W

Trang 19

398.0 [15.67]

630.0 [24.8]

290.0

1403.0 [55.24]

26.5[1.04]

25.0

Trang 21

404.0 [15.91]

630.0 [24.8] [19.69]500.0 630.0[24.8]

760.0[29.92]

800.0[31.5] -

1729.0 [68.07] 1701.6 [66.99] - -

H3 - 51.0 38.0 65.0 204.0 68.0 137.0 13.0 26.5 25.0 22.0 34.0 117.5

Trang 22

Digital Keypad

KPC-CC01

Trang 23

prevent the risk of fire accident.

 Install the AC motor drive in Pollution Degree 2 environments only: normallyl only

nonconductive pollution occurs and temporary conductivity caused by condensation is

expected

The appearances shown in the following figures are for reference only

Airflow direction: (Blue arrow) inflow (Red arrow) outflow

Single drive installation

(Frame A-H) Side-by-side installation(Frame A-C)

Multiple drives, side-by-side installation(Frame A,B,C, G, H)

Trang 24

Multiple drives, side-by-side installation (Frame D, E, F) Install metal separation between the drives

Multiple drives side-by-side installation and in rows (Frame A,B,C )

Ta: Frame A~G Ta*: Frame H

When installing one AC motor drive below another one (top-bottom installation), use a metal separation between the drives to prevent mutual heating The temperature measured at the fan’s inflow side must be lower than the temperature measured at the operation side If the fan’s inflow temperature is higher, use

a thicker or larger size of metal seperature Operation temperature is the temperature measured at 50mm away from the fan’s inflow side (As shown in the figure below)

Minimum mounting clearance

Trang 25

VFD370CH43A-00/21, VFD450CH43A-00/21, VFD550CH43A-00/21, VFD750CH43A-00/21

Frame E VFD450CH23A-00/21, VFD550CH23A-00/21, VFD900CH43A-00/21, VFD1100CH43A-00/21

Frame F VFD750CH23A-00/21, VFD1320CH43A-00/21

Frame G VFD1600CH43A-00/21, VFD1850CH43A-00/21, VFD2200CH43A-00/21

Frame H VFD2800CH43A-00, VFD2800CH43C-00, VFD2800CH43C-21

NOTE

1 The minimum mounting clearances stated in the table above applies to AC motor drives frame A to D A drive

fails to follow the minimum mounting clearances may cause the fan to malfunction and heat dissipation problem

NOT E

※ The mounting clearances stated in the figure is for installing the drive in an open area To install the drive in a confined space (such as cabinet or electric box), please follow the following three rules: (1) Keep the minimummounting clearances (2) Install a ventilation equipment or an air

conditioner to keep surrounding temperature lower than operation temperature (3) Refer to parameter setting and set up Pr 00-16, Pr.00-17, and Pr 06-55

※ The following table shows the heat dissipation and the required air volume when installing a single drive in a confined space When installing multiple drives, the required air volume shall be multiplied

by the number the drives

※ Refer to the chart (Air flow rate for cooling) for ventilation equipment design and selection

※ Refer to the chart (Power dissipation) for air conditioner design and selection

Air flow rate for cooling Power dissipation of AC

motor drive Flow Rate (cfm) Flow Rate (m3/hr) Power Dissipation

Model No

External Internal Total External Internal Total

Loss External (Heat sink)

Trang 26

Air flow rate for cooling Power dissipation of

AC motor drive Flow Rate (cfm) Flow Rate (m3/hr) Power Dissipation

Model No

External Internal Total External Internal Total

Loss External (Heat sink)

※ When installing the multiple drives, the required air volume should be the

required air volume for single drive X the number of the drives

※ The heat dissipation shown

in the chart is for installing single drive in a confined space

※ When installing the multiple drives, volume of heat dissipation should

be the heat dissipated for single drive X the number of the drives

※ Heat dissipation for each model is calculated by rated voltage, current and default carrier

Trang 27

Derating Curve Diagram (Pr.00-16=0)

Trang 28

Chapter 3 Unpacking

The AC motor drive should be kept in the shipping carton or crate before installation In order to retain the warranty coverage, the AC motor drive should be stored properly when it is not to be used for an

extended period of time

The AC motor drive is packed in the crate Follows the following step for unpack:

Frame D

Loosen the 12 cover screws to open the crate

Loosen the 4 screws on the iron plates There are 4

iron plates and in total of 16 screws

Remove the EPEs and manual

Loosen the 8 screws that fastened on the pallet

and remove the wooden plate

Remove the crate cover, EPEs, rubber and manual

Trang 29

Lift the drive by hooking the lifting hole It is now

ready for installation

Loosen the 10 screws on the pallet, remove the wooden plate

Lift the drive by hooking the lifting hole It is now ready for installation

Frame E

Loosen the 4 screws on the iron plates There are 4

iron plates and in total of 16 screws

Loosen the 4 screws on the iron plates There are

4 iron plates and in total of 16 screws

Trang 30

Remove the crate cover, EPEs and manual Remove the crate cover, EPEs, rubbers and

Lift the drive by hooking the lifting hole It is now

ready for installation

Lift the drive by hooking the lifting hole It is now ready for installation

Trang 31

Frame F

Remove the 6 clips on the side of the crate with a

flat-head screwdriver (As shown in figure below.)

Remove the 6 clips on the side of the crate with a flat-head screwdriver (As shown in figure below.)

6

5 4

1 2

3Remove the crate cover, EPEs and manual Remove the crate cover, EPEs, rubbers and

manual

Loosen the 5 screws on the pallet

as shown in the following figure

1 2 3 4 5

Loosen the 9 screws on the pallet and remove the wooden plate

123456789

wood plate1wood plate2

Trang 32

Lift the drive by hooking the lifting hole It is now

ready for installation

Lift the drive by hooking the lifting hole It is now ready for installation

Frame G

Remove the 6 clips on the side of the crate with a

flathead screwdriver (As shown in figure below.)

1

2

3

4 5

6

Remove the crate cover, EPEs and manual Remove the crate cover, EPEs, rubber and manual

Trang 33

Loosen the 5 screws as shown in following figure:

1

2

3 4 5

Loosen the 9 screws and remove the wooden plate

wood plate5

wood plate1 3

2

4 11 7 9

6 8 10 12

wood plate2 wood plate3

1

wood plate4

Lift the drive by hooking the lifting hole It is now

ready for installation

Remove the 8 clips on the side of the crate with a

flathead screwdriver (As shown in figure below.)

Remove the 8 clips on the side of the crate with a flathead screwdriver (As shown in figure below.)

Trang 34

Remove the crate cover, EPEs and manual Remove the crate cover, EPEs, rubbers and

manual

Loosen the 6 screws on the top then remove 6

metal washers and 6 plastic washers as shown in

figure below

Loosen the 6 screws on the top then remove 6 metal washers and 6 plastic washers as shown in figure below

Lift the drive by hooking the lifting hole It is now

ready for installation

Loosen 6 of the M6 screws on the side and remove the 2 plates, as shown in below The removed screws and plates can be used to secure the AC motor drive from the external

Trang 35

Secure the drive from the external (Skip to the

next step if this situation does not apply to you.) Loosen 8 of M8 screws on the both sides and place the 2 plates that were removed from the last step Fix the plates to AC motor drive by fasten 8 of the M8 screws (As shown in below)

Trang 36

Remove the crate cover, EPEs, rubber and manual

Loosen the 6 screws on the cover, remove 6 metal washers and 6 plastic washers as shown in below:

Loosen 6 of the M6 screws on the side and removes the 2 plates, as shown in following figure The removed screws and plates can be used to secure AC motor drive from the external

Trang 37

Secure the drive from the internal

Loosen 18 of the M6 screws and remove the top

cover as shown in figure 2 Mount the cover (figure

1) back to the drive by fasten the M6 screws to the

two sides of the drive, as shown in figure 2

Torque: 35~45kg-cm (30.38~39.06lb-in.)

Figure 1 Top cover (Use M12 screws)

Secure the drive from the external

Loosen 8 of the M8 screws on the both sides and place the 2 plates that were removed from the last step Fix the plates to rive by fasten 8 of the M8 screws (As shown in figure below)

Torque: 150~180kg-cm (130.20~156.24lb-in.)

Figure 2Fasten 6 of the M6 screws back to the original position where it was removed As shown in the figure:

Trang 38

Lift the drive by hooking the lifting hole It is now ready for installation.

Frame H Secure the drive

(VFDXXXXCHXXA-00)

Screw: M12*6

Torque: 340-420kg-cm [295.1-364.6lb-in.]

Trang 39

(VFDXXXXCHXXC-00)

Secure the drive from the internal

Screw: M12*8 Torque: 340-420kg-cm [295.1-364.6lb-in.]

(VFDXXXXCHXXC-21)

Secure the drive from the external Screw: M12*8

Torque: 340-420kg-cm [295.1-364.6lb-in.]

Trang 40

The Lifting Hook

The arrows indicate the location of the lifting holes of frame D to H, as shown in figure below: