Building Name: Parking Structure #1Building Address: Detroit Michigan Owner: Wayne State University Audit Date: 10-14-19Building Elevator Number: #051 A Conducted By: Cornell Myers, Jame
Trang 1WAYNE STATE UNIVERSITY PARKING STRUCTURE
ASSESSMENT
C REATED B Y : C ORNELL M YERS
C ORPORATE E LEVATOR A SSET M ANAGEMENT
Trang 2• T ABLE OF C ONTENTS : 2
Trang 3• C ORPORATE E LEVATOR A SSET M ANAGEMENT MADE A VISIT TO YOUR SITES AND COMPILED A DETAILED REPORT OF THE 15 ELEVATORS LOCATED AT FIVE FACILITIES
T HIS A UDIT /I NSPECTION OF ALL THE UNITS STARTED ON O CTOBER 14, 2019 AND CONCLUDED ON O CTOBER 16, 2019 W E USED LICENSED INSPECTORS TO PROVIDE A THOROUGH INSPECTION OF EACH UNIT
•
• T HIS TEAM HAS OVER 60 YEARS OF HANDS ON EXPERIENCE WITHIN THE ELEVATOR INDUSTRY AND IS LICENSED BY BOTH THE S TATE OF M ICHIGAN AND THE C ITY OF
D ETROIT E LEVATOR S AFETY D IVISIONS AS WELL AS A N ATIONAL QEI (Q UALITY
E LEVATOR I NSPECTOR ) CERTIFICATION CAPABLE OF REVIEWING THE INSTALLATION ,
MODERNIZATION , AND MAINTENANCE OF ALL ELEVATORS AND ESCALATORS IN THE
OF D ETROIT IS THE AHJ (A UTHORITY H AVING J URISDICTION ) T HIS REPORT ALSO CONTAINS PHOTOS AND A WRITTEN PUNCH LIST OF DEFICIENCIES FOR THE UNITS WE INSPECTED
MONTHLY VISITS BUT THE VISITS MADE ARE MERELY VISUAL INSPECTIONS WITH NO
•
• I T SHALL ALSO BE NOTED THAT IF THE ELECTRONIC MAINTENANCE REPORT SHOWS THAT THEY ARE ACTUALLY PERFORMING MAINTENANCE ITEMS IT DOES NOT FULLY COORDINATE WITH THE MAINTENANCE DOCUMENTS POSTED IN THE MACHINE ROOMS
T HIS IS CONCERNING AS THE MACHINE ROOM LOGS ARE CODE REQUIRED DOCUMENTS THAT ARE TO INDICATE ALL MAINTENANCE BEING PERFORMED ON THE UNIT
Trang 4• M AINTENANCE C ONTRACT
• T HE TYPE OF MAINTENANCE CONTRACTS YOU HAVE WITH S CHINDLER E LEVATOR ARE “F ULL
M AINTENANCE A GREEMENTS ” WHICH COVER ALL COMPONENTS , BOTH ELECTRICAL AND
MECHANICAL OF YOUR ELEVATORS WITH EXCEPTIONS FOR VANDALISM , ABUSE OF EQUIPMENT AND OBSOLETE EQUIPMENT W ITH PROPER MAINTENANCE , THIS CONTRACT SHOULD PROVIDE W AYNE
S TATE U NIVERSITY WITH ADEQUATE PREVENTIVE MAINTENANCE
PERFORMANCE AS WELL AS THE LIFESPAN OF YOUR EQUIPMENT W E RECOMMEND THAT YOU PROVIDE OUR PUNCH LIST OF DEFICIENCIES TO YOUR SERVICE PROVIDER AND INSTRUCT THEM TO CORRECT THE ITEMS IN THE NEXT 30 - 60 DAYS M OST OF THE ITEMS SHOULD BE COVERED BY YOUR CONTRACT AND SHOULD BE CORRECTED AT NO COST TO W AYNE S TATE U NIVERSITY T HE EXCEPTION IS THE EQUIPMENT DEEMED OBSOLETE BY YOUR SERVICE PROVIDER OR REPAIRS REQUIRED DUE TO THE INFLUENCE OF WATER PENETRATING THE HOISTWAY E VEN WITH THE OBSOLETE EQUIPMENT , THE LABOR SHOULD BE COVERED IN YOUR CONTRACT WITH NO COST
•
• R EPLACING ELEVATORS WITH TODAY ’ S NEW TECHNOLOGY MAKES THESE UNITS CLEANER ,
GREENER , SAFER AND MORE ENERGY EFFICIENT I T ALSO REDUCES THE COST OF BILLABLE
REPAIRS TO THE ELEVATORS AND PROVIDES A MORE ENJOYABLE EXPERIENCE FOR YOUR
CUSTOMERS AND IMPROVES THE OVERALL IMAGE OF THE BUILDING
AN ANNUAL FIRE SERVICE / SMOKE TEST
Trang 5Conclusion
Elevators are the lifeblood of all multilevel buildings, which is why Corporate Elevator Asset
Management looks at elevators as an asset of the owner, rather than just a function of the building
The major problem facing the elevators we inspected is a lack of maintenance We recommend
Wayne State University has an in-depth discussion with your service provider to address the lack
of maintenance
As mentioned Corporate Elevator looks at elevators as an asset of the owner and we are perfectly
positioned to manage the entire aspect of this asset, from new installation and modernization, to
maintenance, service and repair Through our elevator management program we are able to
conduct regularly scheduled inspections, review “repair / callback” invoices from your service
provider and be available for telephone or face to face meetings
Sincerely,
Cornell Myers
President – Managing Partner
Corporate Elevator Asset Management
Trang 6t WSU Bldg ID
No of
Elevators WSU ID # CITY LICENSE # INSTALL YEAR *ELEVATOR TYPE Elevator Size ADA / Not ADA Priority
Large Maintenance Deficiencies
Contoller Type - OEM or Non-Prop
30 day maintenance Code Compliance - Safety Test CURRENT RATING
Expected Life Cycle Estimated Cost for Modernization
Recommended Modernization Year
Reference Number
COMMENTS
Virginia Controls Non
*oldest units but simple and not yet obsolete on the relays
Virginia Controls Non
*oldest units but simple and not yet obsolete on the relays
MCE - Non
I would have these as the top priority for replacement.
MCE - Non
I would have these as the top priority for replacement.
MCE - Non
MCE - Non
I would have these as the top priority for replacement.
MCE - Non
I would have these as the top priority for replacement.
Need maintained with attention to ropes and machine seals.
Need maintained with attention to the ropes and machine seals.
Vertitron - Non
*glass wall to protect elevator fronts may be necessary.
Vertitron - Non
*glass wall to protect elevator fronts may be necessary.
Vertitron - Non
Maintenance needs to be done regularly with lubrication.
Trang 7City # Elevator Type Hydraulic or Traction
Trang 8Typical Traction Modernization items replaced Typical Hydraulic Modernization items replaced Typical Work by Others included in turnkey
New Hoist Ropes New Power Unit (pump, motor, oil) heating and air conditioning Machine - sometimes retained Jack - if necessary new electrical disconnects if needed
Door tracks and rollers Door tracks and rollers touch up to include all work to fireproof Door protection (microlight) Door protection (microlight) elevator flooring
Oil buffers (when retained - flushed) Spring Buffers (cleaned and painted) purchase cab interiors
Phone shall be replaced Phone shall be replaced GFCI's and outlet for sump pump Car and CWT rollers Car guides to be replaced.
car top inspection station car top inspection station
hoistway access switches hoistway access switches
rope grippers or secondary brake new wiring throughout
selector devices new valve, precise leveling new wiring throughout door headers if needed
Trang 9• L EGEND FOR C OLOR C ODED A UDIT F ORMS
• B LUE – N EEDS ATTENTION BUT DOES NOT H OLD IMMEDIATE THREAT FOR
SHUTTING THE ELEVATOR D OWN
• Y ELLOW – N EEDS ATTENTION TO BE SCHEDULED AND COMPLETED I F NOT ADDRESSED IT COULD POTENTIALLY CAUSE THE ELEVATOR TO MALFUNCTION OR
CREATE AN UNSAFE CONDITION
• R ED – N EEDS IMMEDIATE ATTENTION , THE PROBLEM WILL EITHER CAUSE THE ELEVATOR TO MALFUNCTION OR CREATE A CITY VIOLATION THAT COULD
JEOPARDIZE THE USE OF THE ELEVATOR
Trang 10Building Name: Parking Structure #1
Building Address: Detroit Michigan
Owner: Wayne State University Audit Date: 10-14-19Building Elevator Number: #051 A Conducted By: Cornell Myers, James Boyd
Elevator Machine Type: Geared Traction
Machine OEM: Otis
Number of Ropes: 5 Size: 1/2"
Power Unit: N/A
Rated HP: 15
General Elevator Information
Elevator Type: Passenger
Original OEM: Otis
Original Installation Date: N/A
Last Date of Modification: 2006
Controller Type: Motion Control IMC
Floors Traveled: Front( 6 ) Rear ( 0 )Estimated Travel: 58'
Capacity of Elevator: 2000#
Rated Speed of Elevator: 200 FPM
Elevator Ride Quality X
Acceleration
City Identification: # 8330
Safety Tests: Five Year Date 1-10-18 30 Mo Date _Not Due _
Observations of the Audit
Comments Unsatisfactory
Satisfactory Excellent
Ratings
Door Type: Center Opening GAL
Current Maintenance Provider: Schindler Elevator
XXXXX
Deceleration
Stopping
Leveling (within 1/4")
Car Lighting
Telephone (24 hour monitor)
X Could use more elevator lighting
Door Restrictors
XX
Fire Service (phase I and phase II) Not tested as to the assessment being conducted.Door Protection: Type
Car Speed Up 10% variance of rated speed 199 fpm
Car Speed Down 20% variance of rated speed 197 FPM
Tested
Door Open Time 3.5 seconds
3.52.5 Doors are a bit clunky and fast in the open direction Need adjustment.
Leveling Within 1/4" of landing sill GOOD
Door Close Time 4.0 seconds
*ladder to overhead structure has no toe space on vertical ladder at the top, poses a safety hazard, needs to be pushed out 2"
*machine seals leaking everywhere, this machine needs a full set of seals or replaced
*housekeeping is awful, machine room and cartop need to be cleaned throughly
*Maintenance is severely lacking The charts only show visual inspection with no preventive maintenance being conducted Maintenance needs done
Door Stall Pressure Maximum of 30 20
Additional Comments
*double door locks can become an issue with service The preferred door configuration would be to swap all the headers and relate the doors
Trang 11Secondary Access
Buffers and Safeties
Trang 12*Maintenance has not been conducted and car has not been in operation since July of 2018.
*Need complete door package upgrade to the elevator and hoistway Floor 5 may need new frame along with header and upgrade components
*Machine seals are leaking everywhere and will need a full replacement along with recommended gear oil change
*ladder to overhead structure has no toe space Housekeeping is awful and needs to be taken care of
Door Stall Pressure Maximum of 30 Unable to test as car is out of service
Additional Comments
*Lock out reads that car is out of service due to the 5th floor hoistway door breakdown
Door Open Time 3.5 seconds
Unable to test as car is out of service
Unable to test as car is out of service
Leveling Within 1/4" of landing sill Unable to test as car is out of service
Door Close Time 4.0 seconds
Car Speed Up 10% variance of rated speed Unable to test as car is out of service
Car Speed Down 20% variance of rated speed Unable to test as car is out of service
Car is out of service Visual inspection made on each
Tested Item Being Tested Parameters Results Comments
Door Restrictors
XX
Fire Service (phase I and phase II) X Car is out of service Visual inspection made on each.Door Protection: Micro light Car is out of service Visual inspection made on each
Car is out of service Visual inspection made on each.Signal Fixtures X Car is out of service Visual inspection made on each
XXXXX
Car is out of service Visual inspection made on each.Car is out of service Visual inspection made on each.Car is out of service Visual inspection made on each.Car is out of service Visual inspection made on each.Car is out of service Visual inspection made on each
Deceleration
Stopping
Leveling (within 1/4")
Car Lighting
Telephone (24 hour monitor)
Elevator Ride Quality X Car is out of service Visual inspection made on each.
City Identification #: 8331
Safety Tests: Five Year Date _Elevator Out of Service Since July 2018_30 Mo Date
Observations of the Audit
Comments Unsatisfactory
Satisfactory Excellent
Ratings
Door Type: Center Opening GAL 2 door lock
Current Maintenance Provider: Schindler Elevator
Power Unit: N/A
Rated HP: 15
General Elevator Information
Elevator Type: Passenger
Original OEM: Otis
Original Installation Date:
Last Date of Modification: 2006
Controller Type: MCE IMC
Floors Traveled: Front( 6 ) Rear ( )Estimated Travel: 58'
Capacity of Elevator: 2000Rated Speed of Elevator: 200
Building Name: Parking Structure #1
Building Address: Detroit Michigan
Owner: Wayne State University Audit Date: 10-14-19Building Elevator Number: 051 B Conducted By: Cornell Myers, James Boyd
Elevator Machine Type: Geared Traction
Machine OEM: OtisNumber of Ropes: 5 Size: 1/2
Trang 13Corroded Door
Equipment
Trang 14*Elevator Layout is odd for parking lot one with elevators named B at the same building Recommnedation would be to go 1-5.
*Machine room could use cleaning and painting along with the adjoining pit
*Machine room door is missing the lock The upper door is locked, however the actual machine room door does not have a lock
*Could not find a machine room log for 2019 2018 looked to be in tact but still has no actual maintenance being completed
Door Stall Pressure Maximum of 30 20
Additional Comments
*Machine upgrade with rope gripper This is a great thing to have on every car and needs to be an upcoming push for the campus Saves Lives
Door Open Time 3.5 seconds
3.52.5 *clunky and could use adjusting to make it smooth.
Leveling Within 1/4" of landing sill Good
Door Close Time 4.0 seconds
Car Speed Up 10% variance of rated speed 199
Car Speed Down 20% variance of rated speed 197
Tested Item Being Tested Parameters Results Comments
Door Restrictors
xx
Fire Service (phase I and phase II) x
Door Protection: Type
.04g's.07g's.01g's
*Cabs are dark with the style and lighting
XXXXXx
Deceleration
Stopping
Leveling (within 1/4")
Car Lighting
Telephone (24 hour monitor)
Elevator Ride Quality X
Acceleration
City Identification #: 8332
Safety Tests: Five Year Date _1/18 30 Mo Date
Observations of the Audit
Comments Unsatisfactory
Satisfactory Excellent
Ratings
Door Type: Center Opening GAL with 2 door locks
Current Maintenance Provider: Schindler Elevator
Power Unit: N/A
Rated HP: 15
General Elevator Information
Elevator Type: Passenger
Original OEM: OTIS
Original Installation Date:
Last Date of Modification: 2006
Controller Type: MCE IMC
Floors Traveled: Front( 6 ) Rear ( )Estimated Travel: 58'
Capacity of Elevator: 2000Rated Speed of Elevator:
Building Name: Parking Structure #1
Building Address: Detroit Michigan
Owner: Wayne State University Audit Date: 10-14-19Building Elevator Number: 051-B? (3) Conducted By: Cornell Myers, James Boyd
Elevator Machine Type: Geared Traction
Machine OEM: Hollister WhitneyNumber of Ropes: 5 Size: 1/2
Trang 16PICTURES OF ELEVATOR 8332
051-3
Corrosion on car platform
Machine Room Lock must be replaced
Selector Tape has accumulated
corrosion
Trang 17*2019 Log was not present I am not sure as to when the elevator had been taken out of service.
*Machine seals are leaking all over Need to have all seals replaced and gear oil replaced before putting elevator back into service
*elevator motor drive is sitting on the machine room floor, must be repaired or replaced to put the elevator back into service
Door Stall Pressure Maximum of 30 Unable to test as car is out of service
Additional Comments
*Lockout does not specify the outage of the elevator, however the drive for the controller is sitting in the MR
Door Open Time 3.5 seconds
Unable to test as car is out of service
Unable to test as car is out of service
Leveling Within 1/4" of landing sill Unable to test as car is out of service
Door Close Time 4.0 seconds
Car Speed Up 10% variance of rated speed Unable to test as car is out of service
Car Speed Down 20% variance of rated speed Unable to test as car is out of service
Car is out of service Visual inspection made on each
Tested Item Being Tested Parameters Results Comments
Door Restrictors
XX
Fire Service (phase I and phase II) X Car is out of service Visual inspection made on each.Door Protection: Type Car is out of service Visual inspection made on each
Car is out of service Visual inspection made on each.Signal Fixtures X Car is out of service Visual inspection made on each
XXXXX
Car is out of service Visual inspection made on each.Car is out of service Visual inspection made on each.Car is out of service Visual inspection made on each.Car is out of service Visual inspection made on each.Car is out of service Visual inspection made on each
Deceleration
Stopping
Leveling (within 1/4")
Car Lighting
Telephone (24 hour monitor)
Elevator Ride Quality X Car is out of service Visual inspection made on each.
City Identification #: 8333
Safety Tests: Five Year Date 30 MO Date
Observations of the Audit
Comments Unsatisfactory
Satisfactory Excellent
Ratings
Door Type: Center Opening GAL double door lock
Current Maintenance Provider: Schindler Elevator
Power Unit: N/A
Rated HP: 15
General Elevator Information
Elevator Type: Passenger
Original OEM: Otis
Original Installation Date:
Last Date of Modification: 2006
Controller Type: MCE IMC
Floors Traveled: Front( 6 ) Rear ( )Estimated Travel: 58'
Capacity of Elevator: 2000Rated Speed of Elevator: 200
Building Name: Parking Structure #1
Building Address: Detroit Michigan
Owner: Wayne State University Audit Date: 10-14-19Building Elevator Number: 051-A (4) Conducted By: Cornell Myers, James Boyd
Elevator Machine Type: Geared Traction
Machine OEM: OtisNumber of Ropes: Size:
Trang 18Machine Leaks
Trang 19Elevator Left out of Service.
Trang 20*roller guide is rusted out of adjustment Need to to break free and lubricate the rollers.
*all electrical covers need to be installed
*machine seals need to be replaced immediately While machine is having seals replaced, the gear oil should be replaced
*September was the only maintenance visit recorded for 2019
Door Stall Pressure Maximum of 30 22
Additional Comments
*signals are missing some fasteners
Door Open Time 3.5 seconds
3.52.5 *doors speed open, need to smooth the open speed
Leveling Within 1/4" of landing sill good
Door Close Time 4.0 seconds
Car Speed Up 10% variance of rated speed 205
Car Speed Down 20% variance of rated speed 207
Tested Item Being Tested Parameters Results Comments
Door Restrictors
xx
Fire Service (phase I and phase II) x
Door Protection: Type
Signal Fixtures x *alarm bell did not work
.05g's.04g's.02g's
xxxxxx
Deceleration
Stopping
Leveling (within 1/4")
Car Lighting
Telephone (24 hour monitor)
Elevator Ride Quality x
Acceleration
City Identification #: 8334
Safety Tests: Five Year Date _1/2018 _30 Mo Date
Observations of the Audit
Comments Unsatisfactory
Satisfactory Excellent
Ratings
Door Type: Center Opening GAL 2 door lock system
Current Maintenance Provider: Schindler Elevator
Power Unit: N/A
Rated HP: 15
General Elevator Information
Elevator Type: Passenger
Original OEM: Otis
Original Installation Date:
Last Date of Modification: 2006
Controller Type: MCE IMC
Floors Traveled: Front( 6 ) Rear ( )Estimated Travel: 58'
Capacity of Elevator: 2000Rated Speed of Elevator: 200
Building Name: Parking Structure #1
Building Address: Detroit Michigan
Owner: Wayne State University Audit Date: 10-14-15Building Elevator Number: 051-5 Conducted By: Cornell Myers, James Boyd
Elevator Machine Type: Geared Traction
Machine OEM: OtisNumber of Ropes: 5 Size: 1/2
Trang 21Roller Guide Spring corroded
Trang 22One visual inspection in 2019
Trang 23*car riding lantern stays illuminated in the up direction
*machine seals are leaking excessively Need to be replaced
Door Stall Pressure Maximum of 30 22
Additional Comments
*controller is marked with the incorrect City#
Door Open Time 3.5 seconds
3.52.5
Leveling Within 1/4" of landing sill good
Door Close Time 4.0 seconds
Car Speed Up 10% variance of rated speed 198
Car Speed Down 20% variance of rated speed 197
Tested Item Being Tested Parameters Results Comments
Door Restrictors
xx
Fire Service (phase I and phase II) x
Door Protection: Type
*phone not operatingx
.08g's.08g's.02g's
xxxxx
City Identification #: 8896
Safety Tests: Five Year Date _7/5/16 _30 Mo Date _DUE _
Observations of the Audit
Comments Unsatisfactory
Satisfactory Excellent
Ratings
Door Type: Center Opening GAL
Current Maintenance Provider: Schindler Elevator
*Car lantern not working properly
Building Name: Parking Structure #2
Building Address: Detroit Michigan
Owner: Wayne State University Audit Date: 10-16-19Building Elevator Number: Northeast Conducted By: Rodger Rowley, James Boyd
Elevator Machine Type: Geared Traction
Machine OEM: Hollister WhitneyNumber of Ropes: 6 Size: 1/2Power Unit: N/A
Rated HP: 15
General Elevator Information
Elevator Type: Passenger
Original OEM:
Original Installation Date: N/A
Last Date of Modification: 2006
Controller Type: MCE IMC
Floors Traveled: Front( 6 ) Rear ( )Estimated Travel: 58'
Capacity of Elevator: 2500Rated Speed of Elevator: 200
Elevator Ride Quality