• Check for the difference in calculation with 5 bus and 3 bus equivalent system when calculating transient problems TRV, MOV ...=> From there, it is clear that the need to calculate tra
Trang 1Tp HCM, September, 2020
Trang 31 PURPOSE
Trang 4• Check for the difference in calculation with 5 bus and 3 bus equivalent system when calculating transient problems (TRV, MOV )
=> From there, it is clear that the need to calculate transient problems with a large system in order to increase the reliability and accuracy of the results.
4
1 PURPOSE
Trang 52 THEORETICAL BASIS
Trang 6• Thevenin's theorem allows to replace a complex circuit with a simple circuit consisting of only one source and one resistor.
6
2 Theoretical basis
2.1 Thevenin's theorem
Trang 7Using Thevenin's theorem is especially advantageous when:
• Focus on a specific part of a circuit The rest of the circuit can be replaced with a simple Thevenin equivalent circuit.
• Using the Thevenin equivalent avoids having to analyze complex circuits.
2 Theoretical basis
2.2 The purpose of Thevenin’s theorem
Trang 8• Thevenin's theorem does not apply to circuits containing nonlinear elements
• Circuit equivalence according to Thevenin's theorem cannot be equivalent in terms of electromagnetic induction between components in the power system.
8
2 Theoretical basis
2.1 Thevenin’s theorem limitations
Trang 9• For transient problems, the Thevenin’s equivalent model can not be applied Because the wave re-reflection (standing wave) will occurs due to the large system equivalence to the smaller system The larger the simulation system, the smaller the amplitude of the reflected wave becomes.
n=6 bus
Standing waves based on simulation system
Trang 102 Theoretical basis
2.1 Limitations when using Thevenin’s equivalent
• Volt-Ampe characteristics when calculating with circuits with nonlinear elements before and after Thevenin equivalent
Trang 113 CALCULATION MODEL
Trang 123 Calculation model
3.1 Calculation model
• Calculated with normal operation mode in 2020
• Calculation using EMTP software
• The 3 buses equivalent system model includes Doc Soi, Pleiku 2 and Quang Trach
Zth Zth
Zth
Trang 13• The 5 buses equivalent system model includes Doc Soi, Pleiku 2, Quang Trach,
Thanh My and Da Nang
Zth
Zth Zth
Trang 143 Calculation model
3.2 Transposed in 500kV Doc Soi – Pleiku 2 transmission line
Trang 153 Calculation model
3.2 Transposed in 500kV Quang Trach – Doc Soi transmission line
Trang 163 Calculation model
3.3 Calculation fault points
Zth Zth
Trang 17• Calculation of absorbed energy level of MOV with fault points 1,2,3 on the Doc Soi, Pleiku 2 and Quang Trach
Zth
2
Trang 183 CALCULATION RESULT
18
Trang 192 phase short circuit-CB
Doc Soi 3 phase short circuit-CBDoc Soi 2 phase short circuit-CBPleiku 2 3 phase short circuit-CBPleiku 2
Trang 201.6
1.8
22.2
2.4
2.6
2 phase short circuit-CB
Doc Soi 3 phase short circuit-CBDoc Soi 2 phase short circuit-CBPleiku 2 3 phase short circuit-CBPleiku 2
Trang 210.168
0.106
0.4070.547
2 phase short circuit-CB Doc
Soi 3 phase short circuit-CB DocSoi 2 phase short circuit-CBPleiku 2 3 phase short circuit-CBPleiku 2
Trang 222 phase short circuit-CB Doc
Soi 3 phase short circuit-CB DocSoi 2 phase short circuit-CBPleiku 2 3 phase short circuit-CBPleiku 2
Trang 233 phase short-circuit at Quảng Trạch
3 Bus system 5 Bus system
Trang 241 phase short-circuit at Quảng Trạch
3 Bus system 5 Bus system
4 Calculation Result
4.3 Comparison of MOV calculation result
Trang 263 phase short-circuit at Pleiku 2
3 Bus system 5 Bus system
Trang 271 phase short-circuit at Pleiku 2
3 Bus system 5 Bus system
Trang 285 COMMENTS ON THE CALCULATION RESULTS
28
Trang 295 COMMENTS ON THE CALCULATION RESULTS
From the calculation results we have the following comments
• The difference in the TRV, RRRV calculation results between the equivalent system of 3 bus and 5 bus is about 30%.
• The difference in the MOV calculation results between 3 bus and 5 bus equivalent systems is very large (about 100%).
→ The wave-related transient problems (MOV computation) give very different results when the system equivalents are 3 and 5 bus Similar to the results of TRV calculation, RRRV also has a relative difference when calculating with the equivalent system of 3 bus and
5 bus.
Trang 30• W Richter, "Applications of Thevenin's theorem," in Electrical
Engineering, vol 64, no 3, pp 103-105, March 1945, doi:
10.1109/IEEE.1945.6440897.
• A W Love, "Comment on "Limitations of the Thevenin and Norton
equivalent circuits for a receiving antenna"," in IEEE Antennas and
Propagation Magazine, vol 45, no 4, pp 98-99, Aug 2003, doi:
10.1109/MAP.2003.1241317.
• Transient Analysis of Power Systems: Solution Techniques, Tools and
Applications, First Edition.
Edited by Juan A Martinez-Velasco.
Annex B - Dynamic System Equivalents
• https://en.wikipedia.org/wiki/Th%C3%A9venin%27s_theorem
30
REFERENCES DOCUMENT
Trang 31EVN PECC2