MD1501 Series Auxiliary Relay Instruction Manual NR Electric Co , Ltd Preface MD1501 Series Auxiliary Relay i Date 2017 08 17 Preface Introduction This guide and the relevant operating or service manual documentation for the equipment provide full information on safe handling, commissioning and testing of this equipment Documentation for equipment ordered from NR is dispatched separately from manufactured goods and may not be received at the same time Therefore, this guide is provided to ensure.
Trang 1MD1501 Series Auxiliary Relay Instruction Manual
NR Electric Co., Ltd.
Trang 3Before carrying out any work on the equipment, the user should be familiar with the contents of this manual, and read relevant chapter carefully
This chapter describes the safety precautions recommended when using the equipment Before installing and using the equipment, this chapter must be thoroughly read and understood
Health and Safety
The information in this chapter of the equipment documentation is intended to ensure that equipment is properly installed and handled in order to maintain it in a safe condition
When electrical equipment is in operation, dangerous voltages will be present in certain parts of the equipment Failure to observe warning notices, incorrect use, or improper use may endanger personnel and equipment and cause personal injury or physical damage
Before working in the terminal strip area, the equipment must be isolated
Proper and safe operation of the equipment depends on appropriate shipping and handling, proper storage, installation and commissioning, and on careful operation, maintenance and servicing For this reason, only qualified personnel may work on or operate the equipment
Qualified personnel are individuals who:
Are familiar with the installation, commissioning, and operation of the equipment and of the system to which it is being connected;
Are able to safely perform switching operations in accordance with accepted safety engineering practices and are authorized to energize and de-energize equipment and to isolate, ground, and label it;
Are trained in the care and use of safety apparatus in accordance with safety engineering practices;
Are trained in emergency procedures (first aid)
Instructions and Warnings
The following indicators and standard definitions are used:
Trang 4DANGER! means that death, severe personal injury and considerable equipment damage
will occur if safety precautions are disregarded
WARNING! means that death, severe personal and considerable equipment damage
could occur if safety precautions are disregarded
CAUTION! means that light personal injury or equipment damage may occur if safety
precautions are disregarded
NOTICE! is particularly applies to damage to device and to resulting damage of the protected
equipment
DANGER!
NEVER allow a open current transformer (CT) secondary circuit connected to this
device while the primary system is live Open CT circuit will produce a dangerously high voltage that cause death
Do NOT touch the exposed terminals of this device while the power supply is on The
generated high voltage causes death, injury, and device damage
WARNING!
Thirty seconds is NECESSARY for discharging the voltage Hazardous voltage can be
present in the DC circuit just after switching off the DC power supply
CAUTION!
Earthing
Securely earthed the earthing terminal of the device
Operating environment
ONLY use the device within the range of ambient environment and in an
environment free of abnormal vibration
Trang 5 Ratings
Check the input ratings BEFORE applying AC voltage/current and power supply to
the device
Printed circuit board
Do NOT attach or remove printed circuit board if the device is powered on
The firmware may be upgraded to add new features or enhance/modify existing
features, please MAKE SURE that the version of this manual is compatible with the
product in your hand
Copyright © 2017 NR All rights reserved
We reserve all rights to this document and to the information contained herein Improper use in particular reproduction and dissemination
to third parties is strictly forbidden except where expressly authorized
The information in this manual is carefully checked periodically, and necessary corrections will be included in future editions If nevertheless any errors are detected, suggestions for correction or improvement are greatly appreciated
We reserve the rights to make technical improvements without notice
NR ELECTRIC CO., LTD
Headquarters: 69, Suyuan Avenue, Jiangning, Nanjing 211102, China
Manufactory: 18, Xinfeng Road, Jiangning, Nanjing 211111, China
Tel: +86-25-87178888 Fax: +86-25-87178999 Website: www.nrelect.com , www.nrec.com
Trang 6Documentation Structure
The manual provides a functional and technical description of this relay and a comprehensive set
of instructions for the use and application of MD1501 series auxiliary relays
All contents provided by this manual are summarized as below:
5 Commissioning
Introduce how to commission the relay, comprising checks on the calibration and functionality of the relay
6 Maintenance
A general maintenance policy for the relay is outlined
7 Decommissioning and Disposal
A general decommissioning and disposal policy for the relay is outlined
8 Manual Version History
List the instruction manual version and the modification history records
Trang 71 Introduction
Table of Contents
1 Introduction 1-a
1.1 Application 1-1 1.2 Function 1-1 1.3 Features 1-1 1.4 Type 1-1
Trang 9MD1501 series auxiliary relays provide functions as follows:
Trip circuit supervision
Lockout function
Tripping relay function
Repeat relay function (voltage operated or current operated)
AC voltage switching function
Adaptive mounting modes, the relay modules can be accommodated in a casing installed on
a panel as a relay device
High burden of the relay for tripping or closing circuit breaker has strong interference withstand capability
More spare relays can be provided and flexible applied
1.4 Type
MD1501 series auxiliary relays can be classified in following types according to their functions
Table 1.4-1 Types of MD1501 series auxiliary relay
MD1501-551 Trip circuit supervision with current operated auxiliary relay
MD1501-552 Phase segregated trip circuit supervision
MD1501-556 Current operated auxiliary relay (3 elements)
MD1501-561 Bi-stable switching relay
MD1501-571 Electrical reset auxiliary element with internal operating coil supervision (high burden)
Trang 10MD1501-572 Self reset auxiliary relay with electrical reset LED indicator (high burden)
NOTICE!
Devices may be upgraded to amend or enhance functions, please ENSURE that this
manual version is compatible with your devices
Trang 112 Technical Data
Table of Contents
2 Technical Data 2-a
2.1 Electrical Specifications 2-1 2.2 Mechanical Specifications 2-1 2.3 Ambient Temperature and Humidity Range 2-1 2.4 Type Tests 2-1 2.5 Certifications 2-2 2.6 Main Technical Data of Each Relay 2-3
Trang 132.1 Electrical Specifications
Power Supply (Voltage Operated Element)
Rated Voltage 110Vdc, 125Vdc, 220Vdc, 250Vdc
Ripple in the DC auxiliary voltage Max 15% of the DC value IEC 60255-11:1979
Operating condition < 120W
2.2 Mechanical Specifications
Enclosure dimensions (W×H×D) 35.5×173.8×198 (unit: mm)
Trepanning dimensions (W×H) 36.4×154(unit: mm), M3 screw
Weight per relay Approx 1kg
Housing material Aluminum, steel
Location of terminal Back side
Enclosure Protection IEC60529:1989
Rear side, connection terminals IP20
2.3 Ambient Temperature and Humidity Range
Dry cold test IEC 60068-2-1:1974 Test Ad for 16 h at -25°C
Dry heat test IEC 60068-2-2:1990 Test Bd for 16 h at +55°C
Damp heat test, cyclic IEC 60068-2-30:1980 Test Db Two (12+12) hour cycles 95%RH, low
temperature -25°C, high temperature +55°C
2.4.2 Mechanical Tests
Vibration IEC60255-21-1:1988 Class I
Shock and bump IEC 60255-21-2:1988 Class I
Trang 142.4.3 Electrical Tests
Dielectric tests IEC 60255-5:2000 Test voltage 2kV, 50Hz, 1min
Impulse voltage tests IEC 60255-5:2000 Test voltage 5kV, unipolar impulses waveform
1.2/50μs,source energy 0.5J Insulation resistance measurements IEC 60255-5:2000 Isolation resistance >100MΩ, 500Vdc
2.4.4 Electromagnetic Compatibility
1MHz burst disturbance test
IEC 60255-22-1:1988 (idt IEC61000-4-12:1995) Common mode: class III 2.5kV
Differential mode: class III 1.0kV
Radio frequency interference tests
IEC 60255-22-3:2007 class III Frequency sweep
Radiated amplitude-modulated 10V/m (rms), f=80~1000MHz Spot frequency
Radiated amplitude-modulated 10V/m (rms), f=80MHz/160MHz/450MHz/900MHz Radiated pulse-modulated
10V/m (rms), f=900MHz
Electrostatic discharge test
IEC60255-22-2:1996 (idt IEC 61000-4-2:2006) class IV For contact discharge: 8kV
For air discharge: 15kV
Fast transient disturbance tests
IEC 60255-22-4:2002 (idt IEC 61000-4-4:2004) Power supply, I/O, Earth: Class IV, 4kV, 2.5 kHz, 5/50ns Communication terminals: Class IV, 2kV, 5 kHz, 5/50ns
Surge immunity test
IEC 60255-22-5:2002 (idt IEC 61000-4-5:1995) class IV Power supply, AC input, I/O port: 4kV, line to earth; 2kV line to line, 1.2/50us
Conducted RF Electromagnetic
Disturbance
IEC 60255-22-6:2001, Class III Power supply, AC, I/O, Comm Terminal: 10Vrms, 150 kHz~80MHz Power Frequency Magnetic Field
Immunity
IEC 61000-4-8:2001, Class V 100A/m for 1min, 1000A/m for 3s
Trang 15 Products safety(PS): 2014/35/EU, EN60255-27:2014
2.6 Main Technical Data of Each Relay
2.6.1 Main Technical Data of Type MD1501-551
Trip circuit supervision relay
Rated voltage
110Vdc: MD1501-551B 125Vdc: MD1501-551N 220Vdc: MD1501-551A 250Vdc: MD1501-551M
Current of supervision relay coil
<10mA: circuit breaker is closed, the current through relay K1 (220Vdc, 250Vdc)
<20mA: circuit breaker is closed, the current through relay K1 (110Vdc, 125Vdc)
<5mA: circuit breaker is open, the current through relay K1 and K2 (220Vdc, 250Vdc)
<10mA: circuit breaker is open, the current through relay K1 and K2 (110Vdc, 125Vdc)
Output contacts Two normally closed contacts, two normally open contacts
Maximum voltage for contact 380Vac, 250Vdc
Voltage withstand for normally open
Current carrying capacity for contact 8A
Overcurrent capacity for contact 50A@200ms, 20A@0.5s, 10A@3s
Breaking capacity for contact
(L/R=40ms) 1.2A@48Vdc, 0.5A@110Vdc, 0.25A@220Vdc
Current operated relay
Input current
1A~8A: adaptive, S1 and S2 in Figure 3.1-1 are short-circuit in default, S3 and S4 in Figure 3.1-1 are disconnect in default, please refer to Table 3.1-1 to change
Pickup current 0.2A~0.5A: the default value
Rated voltage drop <2V
Output contacts two normally open contacts
Maximum voltage for contact 380Vac, 250Vdc
Voltage withstand for normally open
Current carrying capacity for contact 8A
Overcurrent capacity for contact 50A@200ms, 20A@0.5s, 10A@3s
Trang 16Breaking capacity for contact
(L/R=40ms) 1.2A@48Vdc, 0.5A@110Vdc, 0.25A@220Vdc
2.6.2 Main Technical Data of Type MD1501-552
Rated voltage
110Vdc: MD1501-552B 125Vdc: MD1501-552N 220Vdc: MD1501-552A 250Vdc: MD1501-552M
Current of supervision relay coil
<10mA: circuit breaker is closed, the current through relay K1 (220Vdc, 250Vdc)
<20mA: circuit breaker is closed, the current through relay K1 (110Vdc, 125Vdc)
<5mA: circuit breaker is open, the current through relay K1 and K2 (220Vdc, 250Vdc)
<10mA: circuit breaker is open, the current through relay K1 and K2 (110Vdc, 125Vdc)
Output contacts two normally closed contacts, two normally open contacts
Maximum voltage for contact 380Vac, 250Vdc
Voltage withstand for normally open
Current carrying capacity for contact 8A
Overcurrent capacity for contact 50A@200ms, 20A@0.5s, 10A@3s
Breaking capacity for contact
(L/R=40ms) 1.2A@48Vdc, 0.5A@110Vdc, 0.25A@220Vdc
2.6.3 Main Technical Data of Type MD1501-556
Current operated relay
Input current
1A~8A: adaptive, S11 and S12, S21 and S22, S31 and S32 in Figure
3.3-1 are short-circuit in default, S13 and S14, S23 and S24, S33
and S34 in Figure 3.3-1 are disconnect in default, please refer to
Table 3.3-1 to change
Pickup current 0.2A~0.5A: the default value
Rated voltage drop <2V
Output contacts 3 groups, two normally open contacts per group
Maximum voltage for contact 380Vac, 250Vdc
Voltage withstand for normally open
Current carrying capacity for contact 8A
Overcurrent capacity for contact 50A@200ms, 20A@0.5s, 10A@3s
Trang 17Breaking capacity for contact
(L/R=40ms) 1.2A@48Vdc, 0.5A@110Vdc, 0.25A@220Vdc
2.6.4 Main Technical Data of Type MD1501-561
Rated voltage
110Vdc: MD1501-561B 125Vdc: MD1501-561N 220Vdc: MD1501-561A 250Vdc: MD1501-561M
Output contacts 4 groups of switching contacts, one group of signal contact
Maximum voltage for contact 380Vac, 250Vdc
Voltage withstand for normally open
Current carrying capacity for contact 8A
Overcurrent capacity for contact 50A@200ms, 20A@0.5s, 10A@3s
Breaking capacity for contact
(L/R=40ms) 1.2A@48Vdc, 0.5A@110Vdc, 0.25A@220Vdc
NOTICE!
Please ENSURE the state of bi-stable relays matches with site current status when put
in service
2.6.5 Main Technical Data of Type MD1501-571
High burden electrical reset auxiliary relay:
Rated voltage
110Vdc: MD1501-571B 125Vdc: MD1501-571N 220Vdc: MD1501-571A 250Vdc: MD1501-571M
Rated power consumption
<2W: normally operating condition, the relay does not operate
<120W: the moment that the relay operates
<6W: the relay operates but the initiation contact is still closed
Pickup power >25W: 220Vdc, 250Vdc
>9W: 110Vdc, 125Vdc Current of supervision relay coil 1.5mA
Operating time Maximum value: 10ms, typical value: 6ms
Trang 18normally closed contacts), one group of signal contact Maximum voltage for contact 380Vac, 250Vdc
Voltage withstand for normally open
Current carrying capacity for contact 8A
Overcurrent capacity for contact 50A@200ms, 20A@0.5s, 10A@3s
Breaking capacity for contact
(L/R=40ms) 1.2A@48Vdc, 0.5A@110Vdc, 0.25A@220Vdc
NOTICE!
For the relay, the power is larger at the moment of operating, and the power is less after the operating When testing the relay, users maybe gradually increase the DC voltage subject to the relay under non-operating state, in fact, the power of the relay is larger
under that situation, so each relay should AVOID subjecting to DC voltage for a long
time under non-operating state (not longer than 20s)
2.6.6 Main Technical Data of Type MD1501-572
High burden self reset auxiliary relay:
Rated voltage
110Vdc: MD1501-572B 125Vdc: MD1501-572N 220Vdc: MD1501-572A 250Vdc: MD1501-572M
Rated power consumption
<2W: normally operating condition, the relay does not operate
<120W: the moment that the relay operates
<6W: the relay operates but the initiation contact is still closed
Pickup power >25W: 220Vdc, 250Vdc
>9W: 110Vdc, 125Vdc Current of supervision relay coil 1.5mA
Operating time Maximum value: 10ms, typical value: 6ms
Output contacts Ten groups of output contacts, one group of signal contact
Maximum voltage for contact 380Vac, 250Vdc
Voltage withstand for normally open
Current carrying capacity for contact 8A
Overcurrent capacity for contact 50A@200ms, 20A@0.5s, 10A@3s
Breaking capacity for contact
(L/R=40ms) 1.2A@48Vdc, 0.5A@110Vdc, 0.25A@220Vdc
NOTICE!
For the relay, the power is larger at the moment of operating, and the power is less after
Trang 19the operating When testing the relay, users maybe gradually increase the DC voltage subject to the relay under non-operating state, in fact, the power of the relay is larger
under that situation, so each relay should AVOID subjecting to DC voltage for a long
time under non-operating state (not longer than 20s)
Trang 213 Operation Theory
Table of Contents
3 Operation Theory 3-a
3.1 Type MD1501-551 (Trip circuit supervision relay) 3-1 3.2 Type MD1501-552 (Phase segregated trip circuit supervision relay) 3-3 3.3 Type MD1501-556 (Current operated auxiliary relay) 3-5 3.4 Type MD1501-561 (Bi-stable switching relay) 3-7 3.5 Type MD1501-571 (Electrical reset auxiliary relay, high burden) 3-8 3.6 Type MD1501-572 (Self reset relay with electrical reset LED flag) 3-10
Trang 233.1 Type MD1501-551 (Trip circuit supervision relay)
Schematic diagram of type MD1501-551 is shown in Figure 3.1-1
K1
n20
L2 K3
K2
K4 K3
L1
Supervised circuit
K5
n19 n18
Supervised circuit status indication
K4-2
K4-1 n11
n16
n14 K5-2
K5-1
Contacts of supervision relay
n13 n15
n17
V V V
V
V
52b
Current operated element and output contact (Example of latched connection)
n22 n21
D8
S1 S2 S3 S4
+
-n04
n02 n01
K6-2
K6-1 n03 Contact of current operated relay
n01 n02 n03 n04 n05 n06 n07 n08 n09 n10 n11 n12 n13 n14 n15 n16 n17 n18 n19 n20 n21 n22
K6+
Reserved Reserved
K6-K1+
K2+
K1-
K2-K4-1 K4-1 K4-2 K4-2 K5-1 K5-1 K5-2 K5-2
DC+
DC-K6-1 K6-1 K6-2 K6-2
Figure 3.1-1 Trip circuit supervision relay type MD1501-551
Trip circuit supervision relay
Application
Trip circuit supervision function is accomplished by relay K1~K5, the typical connection is shown
as dotted line part in Figure 3.1-1 An alarm will be given by relays K4 and K5 if any of following
conditions happens
1) DC power supply is lost
2) A fault occurs within the tripping circuit
Principle
Trang 24Relays K1 and K2 can accomplish trip circuit supervision, when the circuit breaker is closed, relay K1 is energized and its normally open contact will make to energize relay K3 When the circuit breaker is open, relays K1 and K2 are energized and their normally open contacts connected in parallel will make to energize relay K3 If any of above mentioned abnormal conditions happens, relays K1 and K2 will drop off, consequently relay K3 drops off to initiate LED indicator L2 and reset relays K4 and K5 as well, alarm outputs are provided by relays K4 and K5 Relay K3 is connected in parallel with a RC circuit providing 300ms delay drop off to prevent mal-operation during transition period of tripping
Principle
Current operated relay K6 is connected in series between an initiation contact and operating device and energized by the through current For the application as a latched element mentioned above, its normally open contact is connected in parallel with the initiation contact (between positive terminal of DC power supply and positive terminal of K6 (i.e n05)) For example of a tripping circuit, protection device operates for an internal fault, K6 will be energized via the protection tripping contact and its normally open contact connected in parallel with tripping contact will close to latch relay K6 until the current path is opened by the circuit breaker auxiliary contact
Tripping contact
Operating device
Figure 3.1-2 Type MD1501-551 is connected with tripping contact as a current latched element
Main technical data of type MD1501-551
Please refer to Section 2.6.1 about main technical data of type MD1501-551
Trang 25Operating current of current operated relay:
Table 3.1-1 Operating current change method of current operated relay of type MD1501-551
Operating current (A) Setting method Pickup current (A)
0.25A disconnect disconnect disconnect disconnect 0.05~0.125
0.50A short-circuit disconnect disconnect disconnect 0.10~0.25
1.00A short-circuit short-circuit disconnect disconnect 0.20~0.50
1.50A short-circuit disconnect short-circuit disconnect 0.30~0.75
2.00A short-circuit short-circuit short-circuit disconnect 0.40~1.00
2.50A short-circuit disconnect disconnect short-circuit 0.50~1.25
3.00A short-circuit short-circuit disconnect short-circuit 0.60~1.50
3.50A short-circuit disconnect short-circuit short-circuit 0.70~1.75
4.00A and above short-circuit short-circuit short-circuit short-circuit 0.80~2.00
3.2 Type MD1501-552 (Phase segregated trip circuit supervision relay)
Schematic diagram of type MD1501-552 is shown in Figure 3.2-1
Trang 26L2 K7
K1
K8 K7
n04 n02 K8-2
K8-1
Contacts of supervision relay
n01
n03
V V V
V V
n22 n21
Phase-B
Phase-C
K3 K4 K5 K6
CB tripping circuitry
52b
52b 52b
52a 52a
52a
n01 n02 n03 n04 n05 n06 n07 n08 n09 n10 n11 n12 n13 n14 n15 n16 n17 n18 n19 n20 n21 n22
K8-1 K8-1 K8-2 K8-2
K1+
K2+
K1- K3+
K2- K4+
K3- K5+
K4- K6+
K5- DC+
K6-
DC-K9-1 K9-1 K9-2 K9-2
Figure 3.2-1 Phase segregated trip circuit supervision relay type MD1501-552
Application
Trip circuit supervision function is accomplished by relay K1~K9 (phase segregated trip circuits
can be supervised simultaneously), the typical connection is shown as dotted line part in Figure
3.2-1 An alarm will be given by relays K8 and K9 if any of following conditions happens
1) DC power supply is lost
2) A fault occurs within the trip circuit of any phase
Principle
Relays K1~K6 can accomplish phase segregated trip circuit supervision (2 relays for each phase, i.e relays K1 and K2 for A phase, relays K3 and K4 for B phase and relays K5 and K6 for C phase) When phase-A of the circuit breaker is closed, relay K1 is energized and its normally open contact will make to energize relay K7 When phase-A of the circuit breaker is open, relays K1 and K2 are energized and their normally open contacts connected in parallel will make to energize relay K7
Takes trip circuit supervision of phase-A as an example, if any of above conditions happens on
Trang 27phase-A circuitry, relays K1 and K2 will drop off, consequently relay K7 drops off to initiate LED indicator L2 and reset relays K8 and K9 as well, similar operation for other phases
Alarm contacts are provided by relays K8 and K9 Relay K7 is connected in parallel with a RC circuit providing 300ms delay drop off to prevent mal-operation during transition period of tripping
Main technical data of type MD1501-552
Please refer to Section 2.6.2 about main technical data of type MD1501-552
3.3 Type MD1501-556 (Current operated auxiliary relay)
Schematic diagram of type MD1501-556 is shown in Figure 3.3-1
Current operated relay 1
n04
n02 n01
K1-2
K1-1 n03
I
n05
n06 K1
K2-2
K2-1 n10
n18
n16 n15
K3-2
K3-1 n17
Current operated relay 2
Current operated relay 3
n01 n02 n03 n04 n05 n06 n07 n08 n09 n10 n11 n12 n13 n14 n15 n16 n17 n18 n19 n20 n21 n22
K1-1 K1-1 K1-2 K1-2 K1+
K1-K3-1 K3-1 K3-2 K3-2 K3+
K3-K2-1 K2-1 K2-2 K2-2 K2+
Trang 28main applications is to connect with tripping or closing contact of protection or control device as a current latched element This can prevent tripping or closing contact of protection or control device from arc breaking
Principle
Current operated relay is connected in series between an initiation contact and operating device and energized by the through current For the application as a latched element mentioned above, its normally open contact is connected in parallel with the initiation contact (between positive terminal of DC power supply and positive terminal of current operated relay (i.e n05, n12 or n19)) The typical application is shown as following diagram, takes relay K1 as an example, if protection device operates for an internal fault, current operated relay will be energized via the protection trip contact and its normally open contact connected in parallel with trip contact will close to latch current operated relay K1 until the current path is opened by the circuit breaker auxiliary contact
Tripping contact
Operating device
Figure 3.3-2 Type MD1501-556 is connected with tripping contact as a current latched element
Main technical data of type MD1501-556
Please refer to Section 2.6.3 about main technical data of type MD1501-556
Operating current of current operated relay:
Operating current of current operated auxiliary relay
Table 3.3-1 Operating current change method of type MD1501-556
Operating current (A)
Setting method
Pickup current (A) K1: S11
K2: S21 K3: S31
K1: S12 K2: S22 K3: S32
K1: S13 K2: S23 K3: S33
K1: S14 K2: S24 K3: S34 0.25A disconnect disconnect disconnect disconnect 0.05~0.125
0.50A short-circuit disconnect disconnect disconnect 0.10~0.25
1.00A short-circuit short-circuit disconnect disconnect 0.20~0.50
1.50A short-circuit disconnect short-circuit disconnect 0.30~0.75
2.00A short-circuit short-circuit short-circuit disconnect 0.40~1.00
2.50A short-circuit disconnect disconnect short-circuit 0.50~1.25
3.00A short-circuit short-circuit disconnect short-circuit 0.60~1.50
3.50A short-circuit disconnect short-circuit short-circuit 0.70~1.75
4.00A and above short-circuit short-circuit short-circuit short-circuit 0.80~2.00
Trang 293.4 Type MD1501-561 (Bi-stable switching relay)
Schematic diagram of type MD1501-561 is shown in Figure 3.4-1
K14-1
Signal contact
n03
n22 n21
Busbar II
K11 K12 K13 K14
K21 K22 K23 K24
The second group of
normally open contact
LED Indication
n05 n04 K24-2
K14-2 n06
n08 n07 K23-1
K13-1 n09
n11 n10 K23-2
K13-2 n12
n13 K12-2 K21-2 K11-2
n17 n18
n19 n20
The second group of
normally closed contact
The first group of
normally open contact
The first group of
normally closed contact
n01 n02 n03 n04 n05 n06 n07 n08 n09 n10 n11 n12 n13 n14 n15 n16 n17 n18 n19 n20 n21 n22
K14-1 K24-1
K14/K24-2 K23-1 K13-2/K23-2
K13-2 K23-2 Both state In
Both In input lost
Device 1 NO Device 1 NC Device 2 NO Device 2 NC DC+
DC-K14-2 K24-2 K13-1/K23-1 K13-1 K14-1/K24-1
Principle
Two relay groups are controlled by double-state auxiliary contacts of two devices respectively Voltage switching of a double-busbar arrangement is taken as an example, voltage of busbar No.1 (BB1) and busbar No.2 (BB2) are connected to the relay output contacts respectively as the sources of voltage signal, the common point of output contacts is connected to a voltage detection element, both normally open and normally closed auxiliary contacts of both busbar 1 and busbar 2 disconnectors are connected to the inputs of the two relay groups (n17, n18, n19 and n20) Except relay K11 and K12, other relays are magnetic latched relays, the relay state will not change even the dc supply is lost, the output status will not be interrupted
Alarm signal output by n13 and n16 indicates the lost of switch-in signals for both bi-stable relays Alarm signal output by n14 and n16 indicates both bi-stable relays in ‘operated state’ that source signals are coupled LED indicator L1 on (Green) indicates the first group bi-stable relays (K12,
Trang 30K13 and K14) in ‘operated state’, LED indicator L2 on (Green) indicates the second group bi-stable relays (K22, K23 and K24) in ‘operated state’
LED indicator
LED indicator L1 (ON BB1): green, it will turn on if the first groups of switching relay operates
LED indicator L2 (ON BB2): green, it will turn on if the second groups of switching relay operates
Main technical data of type MD1501-561
Please refer to Section 2.6.4 about main technical data of type MD1501-561
3.5 Type MD1501-571 (Electrical reset auxiliary relay, high burden)
Schematic diagram of type MD1501-571 is shown in Figure 3.5-1 and Figure 3.5-2
NO contact: normally open contact
NC contact: normally closed contact