Hướng dẫn lập trình kết nối PLC IDEC với màn hình HMI Delta Sơ đồ kết nối và lập trình địa chỉ ô nhớ giữa PLC IDEC và HMI Delta Series HMI Connection Manual IDEC Micro Smart PLC HMI Factory Setting Baud rate 9600 7 Even 1 Controller Station Number 0 (0~31, 255) Control Area Status Area D0D10 Connection a RS 232 (DOP AAEAS, DOP B Series) Definition of PLC ReadWrite Address a Registers Format Type Word No (n) ReadWrite Range Data Length Note input Xn X0 – X290 Word output Yn Y0 – Y290 Word internal relay (ordinary) Mn M0 – M1260 Word internal relay (special) Mn M8000 – M8140 Word shift register Rn R0 – R112 Word Oct.
Trang 1Series HMI Connection Manual
IDEC Micro Smart PLC
HMI Factory Setting:
Baud rate: 9600 7 Even 1
Controller Station Number: 0 (0~31, 255)
Control Area / Status Area: D0/D10
Connection
a RS-232 (DOP-A/AE/AS, DOP-B Series)
Definition of PLC Read/Write Address
a Registers
Format Type
Word No (n) Read/Write Range
Data Length Note
internal relay (ordinary) Mn M0 – M1260 Word
internal relay (special) Mn M8000 – M8140 Word
Counter(Current value) CCn CC0 – CC99 Word
Data register (special) Dn D8000 – D8199 Word
DOP series
9 pin D-sub male (RS-232)
Controller
SG (7) GND (5)
SG (8)
Hướng dẫn kết nối PLC với HMI Delta DOP
www.plc.today
Trang 2Series HMI Connection Manual
b Contacts
Format Type Word No (n)
Bit No (b)
Read/Write Range Note
internal relay (ordinary) Mnnnb M0000 – M1277 1
internal relay (special) Mnnnb M8000 – M8157 1
shift register Rb R0 – R127
Counter Status CSb CS0 – CS99 2
NOTE
1) n represents decimal, b represents octal
2) This type of device is for read only
3) It supports MicroSmart / ONC (OpenNet Controller) / MICRO3 / MICRO3C
4) TSn / CSn can only be used on MicroSmart / ONC (OpenNet Controller)