Hướng dẫn kết nối và lập trình màn hình HMI Delta kết nối với PLC Facon Series HMI Connection Manual Facon FB Series PLC HMI Factory Setting Baud rate 9600, 7, Even, 1 Controller Station Number 1 Control Area Status Area R0R10 Connection a RS 232 (DOP AAEAS, DOP B Series) b RS 232 (DOP AAEAS, DOP B Series) CB(Communication Board) CM(Communication Module), FBs Series Port 1) DOP series 9 pin D SUB (RS 232) Controller 9 pin D SUB male (RS 232) RXD (2) (2) TXD TXD (3) (3) RXD GND (5) (5) GND (8) RTS (7) CTS DOP series 9 pin D SUB (RS 232) Controller 15 pin male.
Trang 1Series HMI Connection Manual
Facon FB Series PLC
HMI Factory Setting:
Baud rate: 9600, 7, Even, 1
Controller Station Number: 1
Control Area / Status Area: R0/R10
Connection
a RS-232 (DOP-A/AE/AS, DOP-B Series)
b RS-232 (DOP-A/AE/AS, DOP-B Series) CB(Communication Board)/ CM(Communication
Module), FBs Series Port 1)
DOP series
9 pin D-SUB (RS-232)
Controller
9 pin D-SUB male (RS-232)
(8) RTS
(7) CTS
DOP series
9 pin D-SUB (RS-232)
Controller
15 pin male (RS-232)
(3) RTS
(4) CTS
Hướng dẫn kết nối PLC với HMI Delta DOP
www.plc.today
Trang 2Series HMI Connection Manual
c RS-232: FBs Series Port 0 (DOP-A/AE/AS, DOP-B Series)
DOP series
9 pin D-SUB (RS-232)
Controller
4 pin Mini DIN male (RS-232)
(3) +5V
Definition of PLC Read/Write Address
a Registers
Format Type
Word No (n) Read/Write Range Data Length Note
b Contacts
Format Type
Bit No (b)
Read/Write Range Note
Trang 3Series HMI Connection Manual
NOTE
1) Device address must be a multiple of 8
Hướng dẫn kết nối PLC với HMI Delta DOP
www.plc.today